UL Instrumentation, 2 Pair 14AWG (7x22) Bare Copper, PVC-NYL Insulation E1 Color Code, Black PVC Outer Jacket, TC-ER NPLF 90C Dry 75C Wet SUN RES DIR BUR
Specifications
Specifications
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Pair(s) | 2 | 14 AWG | 7x22 | BC - Bare Copper |
Insulation
Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
PVC/Nylon - Polyvinyl Chloride + Nylon | 0.024 in (0.61 mm) | 0.116 in (2.95 mm) | ICEA Chart E1 |
Inner Shield
Element | Shield Type | Material | Coverage | Drainwire Type |
---|
Each Pair | Tape | Bi-Laminate (Alum+Poly) | 100% | 18 AWG (7x26) TC |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter |
---|
PVC - Polyvinyl Chloride | 0.063 in (1.6 mm) | 0.564 in |
Electrical Characteristics
Electricals
Nom. Conductor DCR | Nom. Inner Shield DCR | Max. Current |
---|
2.67 Ohm/1000ft | 0.84 Ohm/1000ft (2.8 Ohm/km) | 21 Amps per Conductor at 30ºC |
Voltage
UL Voltage Rating |
---|
600 V (TC-ER), 150 V (NPLF) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
90°C Dry, 75°C Wet | -30°C To +90°C Dry, +75°C Wet |
Bend Radius
Stationary Min. | Installation Min. |
---|
2.24 in (56.9 mm) | 2.8 in |
Max. Pull Tension | 263.2 lbs (119.4 kg) |
---|
Bulk Cable Weight | 146 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial |
---|
Flammability / Reaction to Fire | UL 1685 UL loading, IEEE 1202 FT4 |
---|
NEC / UL Compliance | Article 336, Article 760 |
---|
European Directive Compliance | EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
History
Update and Revision | Revision Number: 0.50 Revision Date: 12-20-2022 |
---|
Documentation
Catalogs
Data Sheets