Fire Alarm Cable, Plenum-FPLP, 4-18 AWG solid bare copper conductors with Flamarrest® insulation, overall Beldfoil® shield, Flamarrest® jacket with ripcord
Specifications
Specifications
Product Overview
Suitable Applications | Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification, Noisy Environment |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 4 | 18 AWG | Solid | BC - Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Conductor(s) | PVC - Polyvinyl Chloride | 0.01 in (0.25 mm) | 0.061 in (1.5 mm) | Black, Red, Brown, Blue |
Outer Shield
Shield Type | Material | Coverage | Drainwire Type |
---|
Tape | Bi-Laminate (Alum+Poly) | 100% | 24 AWG (Solid) TC |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
PVC - Polyvinyl Chloride | 0.015 in (0.38 mm) | 0.18 in | Yes |
Overall Cable Diameter (Nominal) | 0.18 in |
---|
Electrical Characteristics
Electricals
Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Max. Current |
---|
6.65 Ohm/1000ft | 40 pF/ft (130 pF/m) | 72 pF/ft (240 pF/m) | 4 Amps per Conductor at 25ºC |
Voltage
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
75°C | 0°C To +75°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
2.7 in (69 mm) | 2.7 in |
Max. Pull Tension | 83.5 lbs (37.9 kg) |
---|
Bulk Cable Weight | 32 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor |
---|
Flammability / Reaction to Fire | NFPA 262 (UL910) |
---|
NEC / UL Compliance | Article 760, FPLP |
---|
European Directive Compliance | EU CE Mark |
---|
Other Standard Compliance(s) | California State Fire Marshall |
---|
Non-Plenum Number | 5322FL |
---|
History
Update and Revision | Revision Number: 0.312 Revision Date: 05-05-2023 |
---|
Documentation
Product Bulletins
Compliance Documentation
Data Sheets