Fire Alarm Cable, Plenum-FPLP, 4-18 AWG solid bare copper conductors with Flamarrest® insulation, Flamarrest® jacket with ripcord
Specifications
Specifications
Product Overview
| Suitable Applications | Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification |
|---|
Construction Details
Conductor
| Element | Number of Element | Size | Stranding | Material |
|---|
| Conductor(s) | 4 | 18 | Solid | BC - Bare Copper |
Insulation
| Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|
| PVC - Polyvinyl Chloride | 0.008 in (0.20 mm) | 0.057 in (1.4 mm) | Black, Red, Brown, Blue |
Outer Jacket
| Material | Nom. Thickness | Nom. Diameter | Ripcord |
|---|
| PVC - Polyvinyl Chloride | 0.015 in (0.38 mm) | 0.166 in | Yes |
Electrical Characteristics
Electricals
| Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Max. Current |
|---|
| 6.65 Ohm/1000ft | 33.5 pF/ft (110 pF/m) | 4 Amps per Conductor at 25ºC |
Voltage
Mechanical Characteristics
Temperature
| UL Temperature | Operating |
|---|
| 75°C | 0°C To +75°C |
Bend Radius
| Stationary Min. | Installation Min. |
|---|
| 1.32 in (33.5 mm) | 1.32 in |
| Max. Pull Tension | 78.4 lbs (35.6 kg) |
|---|
| Bulk Cable Weight | 28 lbs/1000ft |
|---|
Standards and Compliance
| Environmental Suitability | Indoor |
|---|
| Flammability / Reaction to Fire | NFPA 262 (UL910) |
|---|
| NEC / UL Compliance | Article 760, FPLP |
|---|
| European Directive Compliance | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
|---|
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
|---|
| Other Standard Compliance(s) | California State Fire Marshall |
|---|
| Non-Plenum Number | 5322UL |
|---|
History
| Update and Revision | Revision Number: 0.307 Revision Date: 05-05-2023 |
|---|
Documentation
Product Bulletins
Compliance Documentation
Data Sheets