Fire Alarm Cable, Plenum-FPLP, 10-18 AWG solid bare copper conductors with Flamarrest® insulation, Flamarrest® jacket with ripcord
Specifications
Specifications
Product Overview
Suitable Applications | Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 10 | 18 AWG | Solid | BC - Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Conductor(s) | PVC - Polyvinyl Chloride | 0.01 in (0.25 mm) | 0.0605 in mm | Black, Red, Brown, Blue, Orange, Yellow, Purple, Green, Red/Black, Red/White |
Outer Shield
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
PVC - Polyvinyl Chloride | 0.015 in (0.38 mm) | 0.272 in | Yes |
Overall Cable Diameter (Nominal) | 0.272 in |
---|
Electrical Characteristics
Electricals
Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Max. Current |
---|
6.4 Ohm/1000ft | 29 pF/ft (95 pF/m) | 3.5 Amps per Conductor at 25ºC |
Voltage
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
75°C | 0°C To +75°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
2.176 in (55.27 mm) | 2.176 in |
Max. Pull Tension | 196 lbs (88.9 kg) |
---|
Bulk Cable Weight | 73.5 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor |
---|
Flammability / Reaction to Fire | NFPA 262 (UL 910) |
---|
NEC / UL Compliance | Article 760, FPLP |
---|
European Directive Compliance | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
Other Standard Compliance(s) | California State Fire Marshall |
---|
Non-Plenum Number | 5328UL |
---|
History
Update and Revision | Revision Number: 0.306 Revision Date: 05-05-2023 |
---|
Documentation
Product Bulletins
Compliance Documentation
Data Sheets