Security & Commercial Audio Cable, 3 Conductor 20 AWG stranded (7x28) tinned copper conductors with Flamarrest® insulation, Flamarrest® jacket with ripcord, Plenum rated.
Specifications
Specifications
Product Overview
Suitable Applications | Security Systems, Intercom/PA Systems, Sound/Audio Systems, Power Limited Controls, Single Line Telephone |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 3 | 20 AWG | 7x28 | TC - Tinned Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Conductor(s) | PVC - Polyvinyl Chloride | 0.008 in (0.20 mm) | 0.052 in (1.3 mm) | Black, Red, White |
Outer Shield
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
PVC - Polyvinyl Chloride | 0.015 in (0.38 mm) | 0.146 in | Yes |
Overall Cable Diameter (Nominal) | 0.146 in |
---|
Electrical Characteristics
Electricals
Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Max. Current |
---|
11.1 Ohm/1000ft | 32 pF/ft (100 pF/m) | 3.75 Amps per Conductor at 25ºC |
Voltage
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
75°C | -20°C To +75°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
1.46 in (37.1 mm) | 1.46 in |
Max. Pull Tension | 37.8 lbs (17.1 kg) |
---|
Bulk Cable Weight | 16 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor - Plenum, Indoor |
---|
Flammability / Reaction to Fire | NFPA 262 (UL 910), FT6 |
---|
NEC / UL Compliance | Article 800, CMP |
---|
CEC / C(UL) Compliance | CMP |
---|
European Directive Compliance | EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
Non-Plenum Number | 5401UH |
---|
History
Update and Revision | Revision Number: 0.51 Revision Date: 12-20-2022 |
---|
Documentation
Product Bulletins
Catalogs
Technical Resources
Compliance Documentation
Data Sheets