Fire Alarm Cable, Plenum-FPLP,6-22 AWG solid bare copper conductors with Flamarrest® insulation, Flamarrest® jacket with ripcord
Specifications
Specifications
Product Overview
Suitable Applications | Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification |
---|
Physical Characteristics (Overall)
Conductor
AWG | Stranding | Material | No. of Conductors |
---|
22 | Solid | BC - Bare Copper | 6 |
Insulation
Material | Material Trade Name | Nominal Wall Thickness |
---|
PVC - Polyvinyl Chloride | Flamarrest® | 0.009 in |
Color Chart
Number | Color |
---|
1 | Black |
2 | Red |
3 | Brown |
4 | Blue |
5 | Orange |
6 | Yellow |
Outer Shield
Outer Jacket
Material | Material Trade Name | Nominal Diameter | Nominal Wall Thickness | Ripcord |
---|
PVC - Polyvinyl Chloride | Flamarrest® | 0.162 in | 0.015 in | Yes |
Electrical Characteristics
Conductor DCR
Nominal Conductor DCR |
---|
15.7 Ohm/1000ft |
Capacitance
Nom. Capacitance Conductor to Conductor |
---|
25 pF/ft |
Current
Max. Recommended Current [A] |
---|
2 Amps per Conductor at 25ºC |
Voltage
UL Voltage Rating |
---|
300 V RMS |
Temperature Range
UL Temp Rating | 75°C |
---|
Operating Temperature Range | 0°C To +75°C |
---|
Mechanical Characteristics
Bulk Cable Weight | 20.8 lbs/1000ft |
---|
Max. Pull Tension | 46.8 lbs |
---|
Min. Bend Radius/Minor Axis | 1.6 in |
---|
Standards
NEC Articles | Article 760 |
---|
NEC/(UL) Compliance | FPLP |
---|
Other Specification | California State Fire Marshall |
---|
Applicable Environmental and Other Programs
EU Directive Compliance | EU Directive 2003/11/EC (BFR) |
---|
EU CE Mark | Yes |
---|
MII Order #39 (China RoHS) | Yes |
---|
Flammability, LS0H, Toxicity Testing
UL Flammability | NFPA 262 Plenum Flame Test (UL910) |
---|
UL voltage rating | 300 V RMS |
---|
Plenum/Non-Plenum
Related Part Numbers
History
Update and Revision | Revision Number: 0.297 Revision Date: 05-05-2023 |
---|
Documentation
Product Bulletins
Data Sheets