Belden

658GMS - Access Control, 18c (#22-6c Foil, #22-4c, #22-4c, #18-4c), CMP, Banana Peel®

(No reviews yet) Write a Review
SKU:
658GMS
Shipping:
Calculated at Checkout
$0.00

Description

Access Control Cable, Plenum-CMP, 6-22 AWG conductors with Beldfoil® shield, 4-22 AWG conductors, 4-22 AWG conductors, 4-18 AWG conductors, All conductors stranded bare copper with Flamarrest® insulation, Each cable has Flamarrest® jacket, Banana Peel® No overall jacket

Specifications

Specifications

Product Overview

Suitable ApplicationsAccess Control, Security System, Power Limited Controls
PatentThis product has one or more applicable patents. More information on patents can be found at https://www.belden.com/patents.

Construction Details

Conductor

Element DescriptionElementNumber of ElementSizeStrandingMaterial
Card ReaderConductor(s)622 AWG7x30BC - Bare Copper
Door ContactConductor(s)422 AWG7x30BC - Bare Copper
REX/SpareConductor(s)422 AWG7x30BC - Bare Copper
Lock PowerConductor(s)418 AWG7x26BC - Bare Copper

Insulation

Element DescriptionElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Card ReaderConductor(s)PVC - Polyvinyl Chloride0.009 in (0.23 mm)0.047 in (1.2 mm)Black, Red, White, Green, Brown, Blue
Door ContactConductor(s)PVC - Polyvinyl Chloride0.009 in (0.23 mm)0.064 in (1.6 mm)Black, Red, White, Green
REX/SpareConductor(s)PVC - Polyvinyl Chloride0.009 in (0.23 mm)0.064 in (1.6 mm)Black, Red, White, Green
Lock PowerConductor(s)PVC - Polyvinyl Chloride0.010 in (0.25 mm)0.047 in (1.2 mm)Black, Red, White, Green

Inner Shield

Element DescriptionElementShield TypeMaterialCoverageDrainwire Type
Card ReaderConductor(s)TapeBi-Laminate (Alum+Poly)100%24 AWG (7x32) TC
Door ContactConductor(s)No Shield
REX/SpareConductor(s)No Shield
Lock PowerConductor(s)No Shield

Inner Jacket

Element DescriptionElementMaterialNom. ThicknessNom. DiameterRipcordColor
Card ReaderConductor(s)PVC - Polyvinyl Chloride0.017 in (0.43 mm)0.179 in (4.55 mm)YesOrange
Door ContactConductor(s)PVC - Polyvinyl Chloride0.017 in (0.43 mm)0.147 in (3.73 mm)YesWhite
REX/SpareConductor(s)PVC - Polyvinyl Chloride0.017 in (0.43 mm)0.147 in (3.73 mm)YesBlue
Lock PowerConductor(s)PVC - Polyvinyl Chloride0.017 in (0.43 mm)0.19 in (4.8 mm)YesGray

Outer Jacket

Nom. Diameter
0.401 in (10.2 mm)
Table NotesBanana Peel®
Overall Cable Diameter (Nominal)0.401 in (10.2 mm)

Electrical Characteristics

Electricals

Element DescriptionElementNom. Conductor DCRNom. Inner Shield DCRNom. Capacitance Cond-to-CondNom. Capacitance Cond-to-ShieldNom. Capacitance Cond-to-Other (Conds + Shield)Max. Current
Card ReaderConductor(s)16.4 Ohm/1000ft16.19 Ohm/1000ft (53.12 Ohm/km)33 pF/ft (110 pF/m)60 pF/ft (200 pF/m)2.2 Amps per Conductor at 25ºC
Door ContactConductor(s)16.4 Ohm/1000ft (53.8 Ohm/km)25 pF/ft (82 pF/m)60 pF/ft (200 pF/m)2.2 Amps per Conductor at 25ºC
REX/SpareConductor(s)16.4 Ohm/1000ft (53.8 Ohm/km)25 pF/ft (82 pF/m)2.2 Amps per Conductor at 25ºC
Lock PowerConductor(s)6.5 Ohm/1000ft (21 Ohm/km)30 pF/ft (98 pF/m)60 pF/ft (200 pF/m)4 Amps per Conductor at 25ºC

Voltage

UL Voltage Rating
300 V (CMP)

Mechanical Characteristics

Temperature

UL TemperatureOperating
75°C0°C to +75°C

Bend Radius

Stationary Min.Installation Min.
4.01 in (102 mm)4.01 in (102 mm)
Max. Pull Tension213 lbs (96.6 kg)
Bulk Cable Weight94 lbs/1000ft

Standards and Compliance

Environmental SuitabilityIndoor - Plenum, Indoor
SustainabilityProduct Lens™, Environmental Product Declaration (EPD) Available
Flammability / Reaction to FireNFPA 262, UL 910 (Plenum), FT6
CPR ComplianceCPR Euroclass: Eca
NEC / UL ComplianceArticle 800, CMP
CEC / C(UL) ComplianceCMP
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
UK Regulation ComplianceUKCA Mark
APAC ComplianceChina RoHS II (GB/T 26572-2011)
Non-Plenum Number558GMS

Product Notes

NotesCold environment installation: When installing cables that have been stored at ambient temperatures of 32 degrees Fahrenheit (0 degrees Centigrade) or lower, Belden recommends conditioning of the cable for 12 hours at room temperature prior to individual cable leg separation.

History

Update and RevisionRevision Number: 0.486 Revision Date: 01-20-2023
View AllClose

Additional Information

Variant_Options:
Item #|Color|Putup Type|Length|UPC
Variant_Options 658GMS 0001000:
658GMS 0001000|Orange, White, Blue, Gray|Reel|1,000 ft|612825178668
View AllClose