Belden
7122W - MachFlex™, 2+1G C #16 Str BC, PVC-NYL Ins, TPE Jkt, 1000V WTTC, 600V TC-ER
- SKU:
- 7122W
- Shipping:
- Calculated at Checkout
Description
MachFlex™ for High Flex, 2+1G Conductor 16AWG (168(7x24) x38) Bare Copper, PVC-NYL Insulation, TPE Outer Jacket, 1000V WTTC, 600V TC-ER
Specifications
Specifications
Physical Characteristics (Overall)
Conductor
| Element | AWG | Stranding | Material | No. of Conductors |
|---|---|---|---|---|
| 16 | 168x38 | BC - Bare Copper | 2 | |
| Ground Wire | 16 | 168x38 | BC - Bare Copper | 1 |
| Conductor Count | 3 |
|---|
Insulation
| Material | Nominal Diameter |
|---|---|
| PVC/Nylon - Polyvinyl Chloride + Nylon | 0.109 in |
Color Chart
| Number | Color |
|---|---|
| 1 | Black and Numbered 1 |
| 2 | Black and Numbered 2 |
| 3 | Green/Yellow |
Outer Shield
| Material |
|---|
| No Shield |
Outer Jacket
| Material | Nominal Diameter | Nominal Wall Thickness |
|---|---|---|
| TPE - Thermoplastic Elastomer | 0.333 in | 0.047 in |
Electrical Characteristics
Conductor DCR
| Nominal Conductor DCR |
|---|
| 5.7 Ohm/1000ft |
Voltage
| UL Voltage Rating |
|---|
| 1000 V RMS |
| 600 V RMS |
Temperature Range
| UL Temp Rating | 75°C Dry, 90°C Wet |
|---|---|
| Other Temp Range | Flexing: -5°C To +90 °C |
Mechanical Characteristics
| Oil Resistance | Yes |
|---|---|
| Flex Cycle Rating | 10 Million Flexes |
| Bulk Cable Weight | 69 lbs/1000ft |
| Max. Pull Tension | 114 lbs |
| Min. Bend Radius (Continuous Flexing) | 3.3 in |
Standards
| NEC/(UL) Compliance | TC-ER, WTTC |
|---|---|
| CEC/C(UL) Compliance | CIC, TC |
| UL AWM Style Compliance | AWM 20328 |
| CSA AWM Compliance | AWM I/II A/B |
Applicable Environmental and Other Programs
| EU Directive 2000/53/EC (ELV) | Yes |
|---|---|
| EU Directive 2003/96/EC (BFR) | Yes |
| EU Directive 2011/65/EU (RoHS 2) | Yes |
| EU Directive 2012/19/EU (WEEE) | Yes |
| EU Directive 2015/863/EU (RoHS 2 amendment) | Yes |
| EU Directive Compliance | EU Directive 2003/11/EC (BFR) |
| MII Order #39 (China RoHS) | Yes |
Suitability
| Suitability - Non-Halogenated | No |
|---|---|
| Suitability - Oil Resistance | Yes - Oil Res II |
| Suitability - Sunlight Resistance | Yes |
Flammability, LS0H, Toxicity Testing
| UL Flammability | UL1685 UL Loading |
|---|---|
| CSA Flammability | FT4 |
| IEEE Flammability | 1202 |
| UL voltage rating | 1000 V RMS |
Plenum/Non-Plenum
| Plenum (Y/N) | No |
|---|
Related Part Numbers
| Footnote | C - CRATE REEL PUT-UP. |
|---|
History
| Update and Revision | Revision Number: 0.386 Revision Date: 05-05-2023 |
|---|
Documentation
Product Bulletins
- Cabling Solutions for Industrial Applications
- VFD Cables Product Bulletin
- Variable Frequency Drive Cable Solutions Brochure
- MarineTuff Offshore & Marine Cable
Catalogs
Brochures
Case Studies
Warranties
Data Sheets
Additional Information
Variant_Options: |
Item #|Color|Put-Up Type|Length|UPC |
Variant_Options 7122W 003250: |
7122W 003250|Orange|Reel|250 ft|612825182313 |
Variant_Options 7122W 0031000: |
7122W 0031000|Orange|Reel|1,000 ft|612825182306 |
Variant_Options 7122W 0035000: |
7122W 0035000|Orange|Reel|5,000 ft|612825182320 |