DataTuff® 7, 4 Pair AWG 26 Bare Copper - Stranded, Polyethylene insulation, S/FTP - Overall Braid / Individual Foil shielding, PVC jacket , AWM 20121
Specifications
Specifications
Product Overview
| Suitable Applications | harsh environment, IIoT, factory or process automation, video, audio, data communication, etc. | 
|---|
Construction Details
Conductor
| Size | Stranding | Material | Number of Pairs | Number of Element | 
|---|
| 26 AWG | Stranded | BC - Bare Copper | 4 | 8 | 
Insulation
| Material | Nom. Insulation Diameter | Color Code | 
|---|
| PE - Polyethylene (Foam) | 1.05 mm (0.0413 in) | White & Blue, White & Orange, White & Green, White & Brown | 
Cable Core
| Description | 
|---|
| 2 twisted insulated conductors, 4 pairs twisted together left hand lay | 
Inner Shield
| Element | Shield Type | Material | 
|---|
| Individual Shielded Pair | Tape | Bi-Laminate (Alum+Poly) | 
Outer Shield
| Shield Type | Material | 
|---|
| Braid | Tinned Copper (TC) | 
Outer Jacket
| Material | Nom. Diameter | 
|---|
| PVC - Polyvinyl Chloride | 6.8 mm (0.27 in) | 
| Overall Cable Diameter (Nominal) | 6.8 mm (0.27 in) | 
|---|
Electrical Characteristics
Electricals
| Max. Conductor DCR | Max. Mutual Capacitance | Max. Capacitance Unbalance | Nom. Characteristic Impedance | 
|---|
| 145 Ohm/km | 56 pF/m (17 pF/ft) | 160 pF/100m | 100 Ohm | 
Delay
| Max. Delay Skew | Nom. Velocity of Prop. | 
|---|
| 40 ns/100m | 70% | 
High Frequency
| Frequency [MHz] | Max. Insertion Loss (Attenuation) [dB/100m] | 
|---|
| 1 | 2.7 | 
| 4 | 5.5 | 
| 10 | 8.5 | 
| 16 | 10.8 | 
| 20 | 12.1 | 
| 31.25 | 15.2 | 
| 62.5 | 21.8 | 
| 100 | 27.8 | 
| 200 | 40.1 | 
| 300 | 50 | 
| 600 | 73.3 | 
Voltage
| UL Voltage Rating | 
|---|
| 30 V RMS | 
Mechanical Characteristics
Temperature
| Operating | Installation | Storage | 
|---|
| -40°C to +80°C | -15°C To + 60°C | -40°C to +80°C | 
Bend Radius
| Stationary Min. | Installation Min. | 
|---|
| 30 mm (1.2 in) | 65 mm | 
| Max. Pull Tension | 80 N (18 lbf) | 
|---|
Standards and Compliance
| Environmental Suitability | Indoor - Euroclass Eca, Indoor, Oil Resistance | 
|---|
| Flammability / Reaction to Fire | IEC 60332-1-2 | 
|---|
| CPR Compliance | CPR Euroclass: Eca | 
|---|
| AWM Compliance | AWM 20121 | 
|---|
| Data Category | Category 7 | 
|---|
| TIA/EIA Compliance | ANSI/TIA 568.2-D | 
|---|
| ISO/IEC Compliance | ISO/IEC 11801-1 | 
|---|
| CENELEC Compliance | EN 50173-1 | 
|---|
| European Directive Compliance | EU CE Mark | 
|---|
| UK Regulation Compliance | UKCA Mark | 
|---|
History
| Update and Revision | Revision Number: 0.191    Revision Date: 12-20-2022 | 
|---|