LonWorks, 1 Pair AWG 22 Bare Copper - Solid, Polyolefin (PO, PE, PP) insulation, Unshielded shielding, LSZH / FRNC jacket , 300V, Cpr Cca
Specifications
Specifications
Product Overview
| Suitable Applications | LonWorks, instrumentation, Low capacitance |
|---|
Physical Characteristics (Overall)
Conductor
| AWG | Stranding | Material | Nominal Diameter |
|---|
| 22 | Solid | BC - Bare Copper | 0.64 mm |
| Conductor Count | 2 |
|---|
| Total Number of Pairs | 1 |
|---|
Insulation
| Material | Nominal Diameter | Diameter +/- Tolerance | Min. Wall Thickness |
|---|
| PE - Polyethylene | 1.17 mm | 0.05 mm | 0.23 mm |
Color Chart
| Color |
|---|
| White/Blue & Blue/White |
| Table Notes | Ring marking applied |
|---|
Outer Shield
Outer Jacket
| Material | Nominal Diameter |
|---|
| LSZH - Low Smoke Zero Halogen (Flame Retardant) | 5.1 mm |
Electrical Characteristics
Conductor DCR
| Nominal Conductor DCR |
|---|
| 55 Ohm/km |
Capacitance
| Nom. Capacitance Conductor to Conductor |
|---|
| 46 pF/m |
Impedance
| Frequency [MHz] | Nominal Characteristic Impedance |
|---|
| 1 - 20 | 100 Ohm |
High Frequency (Nominal/Typical)
| Frequency [MHz] | Nom. Insertion Loss |
|---|
| 0.772 MHz | 1.3 dB/100m |
| 1 MHz | 1.5 dB/100m |
| 4 MHz | 3.1 dB/100m |
| 10 MHz | 4.9 dB/100m |
| 16 MHz | 6.3 dB/100m |
| 20 MHz | 6.9 dB/100m |
Current
| Element | Max. Recommended Current [A] |
|---|
| Conductor(s) | 2.5 Amps per Conductor |
Voltage
Temperature Range
| Operating Temperature Range | -15°C To +80°C |
|---|
Mechanical Characteristics
| Max. Pull Tension | 50 N |
|---|
| Min. Bend Radius During Installation | 100 mm |
|---|
Standards
| CPR Euroclass | Cca-s1a,d1,a1 |
|---|
Applicable Environmental and Other Programs
| Environmental Space | Indoor - Euroclass Cca |
|---|
Flammability, LS0H, Toxicity Testing
| IEC Flammability | IEC 60332-1-2 |
|---|
| IEC 60754-1 - Halogen Amount | Zero |
|---|
| IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity | 2.5 |
|---|
| IEC 60754-2 - Halogen Acid Gas Amount - Min. pH | 4.3 |
|---|
| IEC 61034-2 - Smoke Density Min. Transmittance | 60% |
|---|
History
| Update and Revision | Revision Number: 0.42 Revision Date: 11-09-2022 |
|---|