LonWorks, 2 Pair AWG 22 Bare Copper - Solid, Polyolefin (PO, PE, PP) insulation, Unshielded shielding, LSZH / FRNC jacket , 300V, CPR Dca
Specifications
Specifications
Product Overview
Suitable Applications | LonWorks, instrumentation, Low capacitance |
---|
Physical Characteristics (Overall)
Conductor
AWG | Stranding | Material | Nominal Diameter | No. of Pairs |
---|
22 | Solid | BC - Bare Copper | 0.64 mm | 2 |
Conductor Count | 4 |
---|
Total Number of Pairs | 2 |
---|
Insulation
Material | Nominal Diameter | Diameter +/- Tolerance | Min. Wall Thickness |
---|
PE - Polyethylene | 1.12 mm | 0.05 mm | 0.23 mm |
Color Chart
Number | Color |
---|
Pair 1 | White/Blue & Blue/White |
Pair 2 | Orange/White & White/Orange |
Table Notes | Ring marking applied |
---|
Outer Shield
Outer Jacket
Material | Nominal Diameter | Diameter +/- Tolerance | Min. Wall Thickness |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | 5.2 mm | 0.4 mm | 0.5 mm |
Construction and Dimensions
Cabling
Description |
---|
2 pairs twisted to cable core |
Electrical Characteristics
Conductor DCR
Nominal Conductor DCR |
---|
55 Ohm/km |
Capacitance
Nom. Capacitance Conductor to Conductor |
---|
46 pF/m |
Impedance
Frequency [MHz] | Nominal Characteristic Impedance |
---|
1 - 20 | 100 Ohm |
High Frequency (Nominal/Typical)
Frequency [MHz] | Nom. Insertion Loss | Nom. NEXT [dB] |
---|
0.772 MHz | 1.3 dB/100m | |
1 MHz | 1.5 dB/100m | 59 dB |
4 MHz | 3.1 dB/100m | 50 dB |
10 MHz | 4.9 dB/100m | 44 dB |
16 MHz | 6.3 dB/100m | 41 dB |
20 MHz | 6.9 dB/100m | 40 dB |
Current
Element | Max. Recommended Current [A] |
---|
Conductor(s) | 2.5 Amps per Conductor |
Voltage
Temperature Range
Operating Temperature Range | -15°C To +80°C |
---|
Mechanical Characteristics
Bulk Cable Weight | 31.2 kg/km |
---|
Max. Pull Tension | 50 N |
---|
Min. Bend Radius During Installation | 80 mm |
---|
Standards
CPR Euroclass | Dca-s1,d1,a1 |
---|
Applicable Environmental and Other Programs
Environmental Space | Indoor - Euroclass Dca |
---|
Flammability, LS0H, Toxicity Testing
IEC Flammability | IEC 60332-1-2, IEC 60332-3-24 |
---|
IEC 60754-1 - Halogen Amount | Zero |
---|
History
Update and Revision | Revision Number: 0.233 Revision Date: 12-19-2022 |
---|
Documentation
Product Bulletins
Catalogs
Brochures
Data Sheets