Safe-T-Line 4 x 2.5 mm2 Fire resistant LPCB approved Multi-conductor, BS 6387 CWZ, EN 50200 PH120, Shielded, Silicone Rubber insulation, Low Smoke Zero Halogen Jacket
Specifications
Specifications
Product Overview
Suitable Applications | Circuit integrity |
---|
Physical Characteristics (Overall)
Conductor
Stranding | Material | No. of Conductors |
---|
Solid | BC - Bare Copper | 4 |
Insulation
Color Chart
Number | Color |
---|
Wire 1 | Blue |
Wire 2 | Brown |
Wire 3 | Black |
Wire 4 | Gray |
Outer Shield
Material | Coverage [%] | Drainwire Material | Drainwire Diameter |
---|
Bi-Laminate (Alum+Poly) | 100% | TC - Tinned Copper | 0.8 mm |
Table Notes | Tape bonded to sheath |
---|
Outer Jacket
Material | Nominal Diameter |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | 11.7 mm |
Electrical Characteristics
Conductor DCR
Nominal Conductor DCR |
---|
7.41 Ohm/km |
Voltage
Voltage Rating [V] |
---|
300/500 V |
Temperature Range
Installation Temperature Range | 0°C To +70°C |
---|
Operating Temperature Range | -40°C To +90°C |
---|
Mechanical Characteristics
Min. Bend Radius During Operation | 6*D |
---|
Standards
CENELEC Compliance | EN 60228 |
---|
Applicable Environmental and Other Programs
EU Directive 2000/53/EC (ELV) | Yes |
---|
EU Directive 2011/65/EU (RoHS 2) | Yes |
---|
Flammability, LS0H, Toxicity Testing
IEC Flammability | IEC 60332-1-2, IEC 60332-3-24, IEC 60332-3-25 |
---|
IEC 60754-1 - Halogen Amount | IEC 60754-1 |
---|
IEC 61034-2 - Smoke Density Min. Transmittance | 60% |
---|
Product Notes
Notes | BS6387 CWZ: C- Fire @ 950°C - 180min, W - Fire & water @ 650°C - 15 + 15 min.,Z - Fire & mechanical shocks @ 950°C -15 min. |
---|
History
Update and Revision | Revision Number: 0.82 Revision Date: 03-14-2023 |
---|