Electronic, 1 Pair AWG 20 Tinned Copper - Stranded, Polyolefin (PO, PE, PP) insulation, Unshielded shielding, LSZH / FRNC jacket , 300V, CPR Cca
Specifications
Specifications
Product Overview
Suitable Applications | Instrumentation and computer cable; For data transmission applications |
---|
Physical Characteristics (Overall)
Conductor
AWG | Stranding | Material | No. of Pairs |
---|
20 | 7x28 | TC - Tinned Copper | 1 |
Conductor Count | 2 |
---|
Total Number of Pairs | 1 |
---|
Insulation
Material | Nominal Diameter | Diameter +/- Tolerance |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | 1.65 mm | 0.05 mm |
Color Chart
Number | Color |
---|
Pair 1 | Black & Red |
Outer Shield
Outer Jacket
Material | Nominal Diameter | Nominal Wall Thickness |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | 4.65 mm | 0.89 mm |
Construction and Dimensions
Cabling
Description |
---|
1 pair covered with a polyester foil |
Electrical Characteristics
Conductor DCR
Nominal Conductor DCR |
---|
32.8 Ohm/km |
Capacitance
Nom. Capacitance Conductor to Conductor |
---|
80.4 pF/m |
Current
Element | Max. Recommended Current [A] |
---|
Conductor(s) | 3.7 Amps per Conductor |
Voltage
Temperature Range
Installation Temperature Range | -15°C To +80°C |
---|
Storage Temperature Range | -45°C To +80°C |
---|
Operating Temp Range (Flexible Install) | -15°C To +80°C |
---|
Operating Temp Range (Fixed Install) | -45°C To +80°C |
---|
Mechanical Characteristics
Oil Resistance | IEC 60811-404 |
---|
Max. Pull Tension | 127 N |
---|
Min. Bend Radius During Installation | 46.5 mm |
---|
Standards
CPR Euroclass | Cca-s2,d1,a1 |
---|
Applicable Environmental and Other Programs
Environmental Space | Indoor - Euroclass Cca |
---|
Suitability
Suitability - Indoor | Yes |
---|
Suitability - Non-Halogenated | Yes |
---|
Suitability - Sunlight Resistance | Yes |
---|
Flammability, LS0H, Toxicity Testing
IEC Flammability | IEC 60332-1-2 |
---|
IEC 60754-1 - Halogen Amount | Zero |
---|
IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity | 2.5 µS/mm |
---|
IEC 60754-2 - Halogen Acid Gas Amount - Min. pH | 4.3 |
---|
IEC 61034-2 - Smoke Density Min. Transmittance | 60% |
---|
History
Update and Revision | Revision Number: 0.29 Revision Date: 11-09-2022 |
---|
Documentation
Product Bulletins
Catalogs
Brochures
Data Sheets