High Temperature Electronic, 6 Conductor 24AWG (7x32) Tinned Copper, FEP Insulation, Overall Beldfoil®+Tinned Copper Braid(85%) Shield, FEP Outer Jacket, CMP
Specifications
Specifications
Product Overview
Suitable Applications | extreme high/low temperature environments; chemical resistant; outdoor and burial applications; low voltage analog signals (4-20ma, 0-10v, ...); low voltage control (24v, …); line level audio; voice communications; panel wiring |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 6 | 24 AWG | 7x32 | TC - Tinned Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Conductor(s) | FEP - Fluorinated Ethylene Propylene | 0.006 in (0.15 mm) | 0.036 in (0.91 mm) | Black, White, Red, Green, Orange, Blue |
Outer Shield
Shield Type | Material | Coverage |
---|
Tape | Bi-Laminate (Alum+Poly) | 100% |
Braid | Tinned Copper (TC) | 85% |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter |
---|
FEP - Fluorinated Ethylene Propylene | 0.014 in (0.36 mm) | 0.167 in (4.24 mm) |
Overall Cable Diameter (Nominal) | 0.167 in (4.24 mm) |
---|
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Max. Current |
---|
Conductor(s) | 24 Ohm/1000ft | 20 pF/ft (66 pF/m) | 36 pF/ft (120 pF/m) | 1.4 Amps per Conductor at 25ºC |
Voltage
UL Voltage Rating |
---|
300 V (CMP) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
150°C | -70°C to +200°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
1.67 in (42.4 mm) | 1.67 in (42.4 mm) |
Max. Pull Tension | 33 lbs (15 kg) |
---|
Bulk Cable Weight | 26 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor - Plenum, Indoor, Outdoor, Sunlight Resistance, Oil Resistance |
---|
Sustainability | CA Prop 65 |
---|
Flammability / Reaction to Fire | NFPA 262, UL 910 (Plenum), FT6 |
---|
NEC / UL Compliance | Article 800, CMP |
---|
CEC / C(UL) Compliance | CMP |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
Product Notes
History
Update and Revision | Revision Number: 0.511 Revision Date: 01-20-2023 |
---|
Documentation
Product Bulletins
Compliance Documentation
Data Sheets