Electronic, 2 Conductor 16AWG (19x29) Tinned Copper, PE Insulation, LSZH Outer Jacket, CPR Cca
Specifications
Specifications
Product Overview
| Suitable Applications | low voltage analog signals (4-20ma, 0-10v, ...); low voltage digital control (24v, …); line level audio; computer communication; panel wiring |
|---|
Physical Characteristics (Overall)
Conductor
| AWG | Stranding | Material | No. of Pairs |
|---|
| 16 | 19x29 | TC - Tinned Copper | 1 |
| Conductor Count | 2 |
|---|
| Total Number of Pairs | 1 |
|---|
Insulation
| Material | Nominal Diameter | Diameter +/- Tolerance | Nominal Wall Thickness |
|---|
| PE - Polyethylene | 2.67 mm | 0.05 mm | 0.018 in |
Color Chart
| Number | Color |
|---|
| Pair 1 | Black & White |
Inner Shield
Inner Jacket
| Nominal Wall Thickness |
|---|
| 0.89 mm |
Outer Shield
Outer Jacket
| Material | Nominal Diameter | Nominal Wall Thickness |
|---|
| LSZH - Low Smoke Zero Halogen (Flame Retardant) | 7.1 mm | 0.89 mm |
Construction and Dimensions
Stranding
Cabling
| Description |
|---|
| 1 pair covered with a polyester foil |
Electrical Characteristics
Conductor DCR
| Nominal Conductor DCR |
|---|
| 14.7 Ohm/km |
Capacitance
| Nom. Capacitance Conductor to Conductor |
|---|
| 52 pF/m |
Inductance
| Nominal Inductance | Nominal Pair Inductance |
|---|
| 0.17 µH/ft | 0.62 µH/m |
Current
| Element | Max. Recommended Current [A] |
|---|
| Conductor(s) | 7.1 Amps per Conductor |
Voltage
Temperature Range
| Installation Temperature Range | -15°C To +80°C |
|---|
| Storage Temperature Range | -45°C To +80°C |
|---|
| Operating Temp Range (Flexible Install) | -15°C To +80°C |
|---|
| Operating Temp Range (Fixed Install) | -45°C To +80°C |
|---|
Mechanical Characteristics
| Oil Resistance | IEC 60811-404 |
|---|
| Max. Pull Tension | 127 N |
|---|
| Min. Bend Radius During Installation | 71 mm |
|---|
| Min. Bend Radius/Minor Axis | 2.5 in |
|---|
Standards
| CPR Euroclass | Cca-s1,d1,a1 |
|---|
| CENELEC Compliance | EN 50290-2-20 |
|---|
Applicable Environmental and Other Programs
| Environmental Space | Indoor - Euroclass Cca |
|---|
| EU Directive Compliance | EU Directive 2003/11/EC (BFR) |
|---|
| EU CE Mark | Yes |
|---|
Suitability
| Suitability - Indoor | Yes |
|---|
| Suitability - Non-Halogenated | Yes |
|---|
| Suitability - Sunlight Resistance | Yes |
|---|
Flammability, LS0H, Toxicity Testing
| IEC Flammability | IEC 60332-1-2 |
|---|
| IEC 60754-1 - Halogen Amount | Zero |
|---|
| IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity | 2.5 µS/mm |
|---|
| IEC 60754-2 - Halogen Acid Gas Amount - Min. pH | 4.3 |
|---|
| IEC 61034-2 - Smoke Density Min. Transmittance | 60% |
|---|
Plenum/Non-Plenum
History
| Update and Revision | Revision Number: 0.26 Revision Date: 11-09-2022 |
|---|
Documentation
Product Bulletins
Catalogs
Brochures
Data Sheets