Electronic, 7 Conductor 16AWG (19x29) Tinned Copper, PVC Insulation, PVC Outer Jacket
Specifications
Specifications
Product Overview
Suitable Applications | Analog Signals & Control (up to 600V); Line Level Audio; Voice Communications; Panel Wiring |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 7 | 16 AWG | 19x29 | TC - Tinned Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Conductor(s) | PVC - Polyvinyl Chloride | 0.031 in (0.79 mm) | 0.121 in (3.07 mm) | Black, White, Red, Green, Orange, Blue, White/Black Stripe |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter |
---|
PVC - Polyvinyl Chloride | 0.045 in (1.1 mm) | 0.458 in (11.6 mm) |
Overall Cable Diameter (Nominal) | 0.458 in (11.6 mm) |
---|
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Max. Current |
---|
Conductor(s) | 4.45 Ohm/1000ft | 19.5 pF/ft (64.0 pF/m) | 9.6 Amps per Conductor at 30ºC |
Voltage
Mechanical Characteristics
Temperature
Bend Radius
Stationary Min. | Installation Min. |
---|
4.6 in (120 mm) | 4.6 in (120 mm) |
Max. Pull Tension | 280 lbs (130 kg) |
---|
Bulk Cable Weight | 132 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor |
---|
Flammability / Reaction to Fire | UL 1581 (VW-1), IEC 60332-1-2 |
---|
CPR Compliance | CPR Euroclass: Eca |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
UK Regulation Compliance | UKCA Mark |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
History
Update and Revision | Revision Number: 0.536 Revision Date: 04-19-2023 |
---|
Documentation
Product Bulletins
Compliance Documentation
Data Sheets