Electronic, 2 Conductor 16AWG (19x29) Tinned Copper, PE Insulation, Overall Beldfoil® Shield, LSZH Outer Jacket, Steel Wire Armour, CPR Eca
Specifications
Specifications
Product Overview
| Suitable Applications | Instrumentation and computer cable for data transmission applications |
|---|
Physical Characteristics (Overall)
Conductor
| AWG | Stranding | Material |
|---|
| 16 | 19x29 | TC - Tinned Copper |
| Conductor Count | 2 |
|---|
| Total Number of Pairs | 1 |
|---|
Insulation
| Material | Nominal Diameter | Diameter +/- Tolerance |
|---|
| PE - Polyethylene | 3.1 mm | 0.07 mm |
Color Chart
| Number | Color |
|---|
| Wire 1 | Black |
| Wire 2 | Transparent |
Inner Shield
| Type | Material | Drainwire Material | Drainwire AWG |
|---|
| Tape | Bi-Laminate (Alum+Poly) | TC - Tinned Copper | 18 |
Inner Jacket
| Material | Color | Nominal Diameter |
|---|
| LSZH - Low Smoke Zero Halogen (Flame Retardant) | Chrome | 8.1 mm |
Outer Shield
| Material |
|---|
| Bi-Laminate (Alum+Poly) |
Outer Jacket
| Material | Nominal Diameter | Nominal Wall Thickness |
|---|
| LSZH - Low Smoke Zero Halogen (Flame Retardant) | 12.5 mm | 1.3 mm |
Construction and Dimensions
Armor
| Type of Armor | Material | Thickness of Armoring Wires | Coverage Percentage |
|---|
| Steel Wire Armoring | Single steel wire | 0.9 mm | 95% |
Electrical Characteristics
Conductor DCR
| Nominal Conductor DCR | Nominal Outer Shield DCR |
|---|
| 14.76 Ohm/km | 20 Ohm/km |
Capacitance
| Nom. Capacitance Conductor to Conductor | Nom. Capacitance Conductor to Shield |
|---|
| 75.4 pF/m | 144.4 pF/m |
Inductance
| Nominal Pair Inductance |
|---|
| 0.66 µH/m |
Current
| Max. Recommended Current [A] |
|---|
| 7 A |
Temperature Range
| Installation Temperature Range | -15°C To +80°C |
|---|
| Storage Temperature Range | -15°C To +80°C |
|---|
| Operating Temperature Range | -15°C To +80°C |
|---|
| Operating Temp Range (Fixed Install) | -45°C To +80°C |
|---|
Mechanical Characteristics
| Oil Resistance | IEC 60811-404 |
|---|
| Bulk Cable Weight | 300 kg/km |
|---|
Standards
| CPR Euroclass | Dca-s1,d2,a1 |
|---|
Applicable Environmental and Other Programs
| Environmental Space | Indoor/Outdoor - Euroclass Dca |
|---|
Flammability, LS0H, Toxicity Testing
| IEC Flammability | IEC 60332-1-2, IEC 60332-3-24 |
|---|
| IEC 60754-1 - Halogen Amount | Zero |
|---|
| IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity | 2.5 µS/mm |
|---|
| IEC 60754-2 - Halogen Acid Gas Amount - Min. pH | 4.3 |
|---|
History
| Update and Revision | Revision Number: 0.179 Revision Date: 12-19-2022 |
|---|
Documentation
Product Bulletins
Catalogs
Brochures
Data Sheets