Electronic, 2 Conductor 16AWG (19x29) Tinned Copper, PE Insulation, Overall Beldfoil® Shield, LSZH Outer Jacket, Steel Wire Armour, CPR Eca
Specifications
Specifications
Product Overview
Suitable Applications | Instrumentation and computer cable for data transmission applications |
---|
Physical Characteristics (Overall)
Conductor
AWG | Stranding | Material |
---|
16 | 19x29 | TC - Tinned Copper |
Conductor Count | 2 |
---|
Total Number of Pairs | 1 |
---|
Insulation
Material | Nominal Diameter | Diameter +/- Tolerance |
---|
PE - Polyethylene | 3.1 mm | 0.07 mm |
Color Chart
Number | Color |
---|
Wire 1 | Black |
Wire 2 | Transparent |
Inner Shield
Type | Material | Drainwire Material | Drainwire AWG |
---|
Tape | Bi-Laminate (Alum+Poly) | TC - Tinned Copper | 18 |
Inner Jacket
Material | Color | Nominal Diameter |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | Chrome | 8.1 mm |
Outer Shield
Material |
---|
Bi-Laminate (Alum+Poly) |
Outer Jacket
Material | Nominal Diameter | Nominal Wall Thickness |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | 12.5 mm | 1.3 mm |
Construction and Dimensions
Armor
Type of Armor | Material | Thickness of Armoring Wires | Coverage Percentage |
---|
Steel Wire Armoring | Single steel wire | 0.9 mm | 95% |
Electrical Characteristics
Conductor DCR
Nominal Conductor DCR | Nominal Outer Shield DCR |
---|
14.76 Ohm/km | 20 Ohm/km |
Capacitance
Nom. Capacitance Conductor to Conductor | Nom. Capacitance Conductor to Shield |
---|
75.4 pF/m | 144.4 pF/m |
Inductance
Nominal Pair Inductance |
---|
0.66 µH/m |
Current
Max. Recommended Current [A] |
---|
7 A |
Temperature Range
Installation Temperature Range | -15°C To +80°C |
---|
Storage Temperature Range | -15°C To +80°C |
---|
Operating Temperature Range | -15°C To +80°C |
---|
Operating Temp Range (Fixed Install) | -45°C To +80°C |
---|
Mechanical Characteristics
Oil Resistance | IEC 60811-404 |
---|
Bulk Cable Weight | 300 kg/km |
---|
Standards
CPR Euroclass | Dca-s1,d2,a1 |
---|
Applicable Environmental and Other Programs
Environmental Space | Indoor/Outdoor - Euroclass Dca |
---|
Flammability, LS0H, Toxicity Testing
IEC Flammability | IEC 60332-1-2, IEC 60332-3-24 |
---|
IEC 60754-1 - Halogen Amount | Zero |
---|
IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity | 2.5 µS/mm |
---|
IEC 60754-2 - Halogen Acid Gas Amount - Min. pH | 4.3 |
---|
History
Update and Revision | Revision Number: 0.179 Revision Date: 12-19-2022 |
---|
Documentation
Product Bulletins
Catalogs
Brochures
Data Sheets