Electronic, 2 Conductor 16AWG (19x29) Tinned Copper, PE Insulation, Overall Beldfoil® Shield, LSZH Outer Jacket, CPR Dca
Specifications
Specifications
Product Overview
Suitable Applications | Analog signals and digital control ; line level audio; voice communications; panel wiring |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 2 | 16 | 19x29 | TC - Tinned Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Conductor(s) | PE - Polyethylene | 0.0285 in (0.724 mm) | 0.116 in (2.95 mm) | Black & Transparent |
Outer Shield
Shield Type | Material | Coverage | Drainwire Type |
---|
Tape | Bi-Laminate (Alum+Poly) | 100% | 18 AWG (16x30) TC |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | 0.032 in (0.81 mm) | 0.3 in (7.6 mm) |
Overall Cable Diameter (Nominal) | 0.3 in (7.6 mm) |
---|
Electrical Characteristics
Electricals
Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Max. Current |
---|
4.5 Ohm/1000ft | 26 pF/ft (85 pF/m) | 46.75 pF/ft (153.4 pF/m) | 7 Amps per Conductor at 25ºC |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
75°C | -20°C To +80°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
3 in (76 mm) | 3 in (76 mm) |
Max. Pull Tension | 100 lbs (45 kg) |
---|
Bulk Cable Weight | 44 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor - Euroclass Dca, Indoor, Non-Halogenated |
---|
Flammability / Reaction to Fire | UL 1685 FT4 Loading |
---|
CPR Compliance | CPR Euroclass: Dca-s2,d1,a1; CPR UKCA Class: Dca-s2,d1,a1 |
---|
NEC / UL Compliance | Article 800 |
---|
ISO/IEC Compliance | IEC 61034-2 - Smoke Density Min Transmittance = 60% |
---|
CENELEC Compliance | EN 50290-2-20 |
---|
European Halogen Free Standards | IEC 62821-1 Halogen Free Compliance = Yes, IEC 60754-1 - Halogen Amount = Zero, IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity = 2.5 µS/mm, IEC 60754-2 - Halogen Acid Gas Amount - Min. pH = 4.3 |
---|
European Directive Compliance | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
UK Regulation Compliance | UKCA Mark |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
History
Update and Revision | Revision Number: 0.537 Revision Date: 03-04-2023 |
---|
Documentation
Product Bulletins
Catalogs
Brochures
Compliance Documentation
Data Sheets