Audio & Instrumentation, 22 AWG stranded (7x30) tinned copper conductors, twisted pairs, polypropylene insulation, individually shielded with 100% Beldfoil® shield (100% coverage), 24 AWG stranded tinned copper drain wire, LSZH jacket.
Specifications
Specifications
Product Overview
| Suitable Applications | shipboard applications; low voltage analog signals (4-20ma, 0-10v, ...); low voltage digital control (24v, …); line level audio; panel wiring | 
|---|
Construction Details
Conductor
| Element | Number of Element | Size | Stranding | Material | 
|---|
| Pair(s) | 2 | 22 AWG | 7x30 | TC - Tinned Copper | 
Insulation
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code | 
|---|
| Pair(s) | PP - Polypropylene | 0.009 in (0.23 mm) | 0.046 in (1.2 mm) | Black & Red, Green & White | 
Inner Shield
| Element | Shield Type | Material | Coverage | Drainwire Type | Notes | 
|---|
| Pair(s) | Tape | Bi-Laminate (Alum+Poly) | 100% | 24 AWG (7x32) TC | foil-out tape on each pair, one drain wire | 
Outer Jacket
| Material | Nom. Thickness | Nom. Diameter | 
|---|
| LSZH - Low Smoke Zero Halogen (Flame Retardant) | 0.034 in (0.86 mm) | 0.196 in (4.98 mm) | 
| Overall Cable Diameter (Nominal) | 0.196 in (4.98 mm) | 
|---|
Electrical Characteristics
Electricals
| Element | Nom. Conductor DCR | Nom. Inner Shield DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current | 
|---|
| Pair(s) | 18.2 Ohm/1000ft | 18.38 Ohm/1000ft (60.30 Ohm/km) | 35 pF/ft (110 pF/m) | 62 pF/ft (200 pF/m) | 45 Ohm | 66% | 2.8 Amps per Conductor at 25ºC | 
Voltage
| UL Voltage Rating | 
|---|
| 300 V (CMG-LS) | 
Mechanical Characteristics
Temperature
| UL Temperature | Operating | 
|---|
| 105°C | -30°C to +105°C | 
Bend Radius
| Stationary Min. | Installation Min. | 
|---|
| 2.0 in (51 mm) | 2.0 in (51 mm) | 
| Max. Pull Tension | 42 lbs (19 kg) | 
|---|
| Bulk Cable Weight | 24 lbs/1000ft | 
|---|
Standards and Compliance
| Environmental Suitability | Indoor/Outdoor, Indoor, Non-Halogenated | 
|---|
| Flammability / Reaction to Fire | UL 1685 FT4 Loading, IEEE 1202, IEC 60332-1-2, IEC 60332-3-22 | 
|---|
| CPR Compliance | CPR Euroclass: Eca | 
|---|
| NEC / UL Compliance | Article 800, CMG-LS | 
|---|
| CEC / C(UL) Compliance | CMG-ST1 | 
|---|
| IEEE Compliance | Std. 45 Clause 23 | 
|---|
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) | 
|---|
| UK Regulation Compliance | UKCA Mark | 
|---|
| APAC Compliance | China RoHS II (GB/T 26572-2011) | 
|---|
Product Notes
| Notes | UL444, ABS Certificate 20-2049434-PDA | 
|---|
History
| Update and Revision | Revision Number: 0.504    Revision Date: 01-20-2023 | 
|---|
Documentation
Product Bulletins
Catalogs
Technical Resources
Compliance Documentation
Data Sheets