Electronic, 2 Conductor 18AWG (16x30) Tinned Copper, PO Insulation, Overall Beldfoil® Shield, LSZH Outer Jacket, CPR B2ca
Specifications
Specifications
Product Overview
Suitable Applications | low voltage analog signals (4-20ma, 0-10v, ...); low voltage digital control (24v, …); line level audio; computer communication; panel wiring |
---|
Physical Characteristics (Overall)
Conductor
AWG | Stranding | Material | No. of Pairs |
---|
18 | 16x30 | TC - Tinned Copper | 1 |
Insulation
Material | Nominal Diameter | Diameter +/- Tolerance |
---|
PE - Polyethylene | 2.08 mm | 0.05 mm |
Color Chart
Number | Color |
---|
Pair 1 | Black & Clear |
Outer Shield
Type | Material | Material Trade Name | Coverage [%] | Drainwire Material | Drainwire AWG | Drainwire Construction n x D |
---|
Tape | Bi-Laminate (Alum+Poly) | Beldfoil® | 100% | TC - Tinned Copper | 20 | 7x28 |
Outer Jacket
Material | Color | Nominal Diameter | Nominal Wall Thickness |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | Chrome (RAL 7037) | 6.0 mm | 0.89 mm |
Electrical Characteristics
Conductor DCR
Nominal Conductor DCR |
---|
21.3 Ohm/km |
Capacitance
Nom. Capacitance Conductor to Conductor | Nom. Capacitance Conductor to Other Conductor to Shield |
---|
98 pF/m | 144 pF/m |
Inductance
Nominal Inductance |
---|
0.591 µH/m |
Current
Element | Max. Recommended Current [A] |
---|
Conductor(s) | 5.2 Amps per Conductor at 25ºC |
Voltage
Temperature Range
Operating Temp Range (Flexible Install) | -15°C To +80°C |
---|
Operating Temp Range (Fixed Install) | -45°C To +80°C |
---|
Mechanical Characteristics
Oil Resistance | IEC 60811-404 |
---|
Max. Pull Tension | 280 N |
---|
Min. Bend Radius/Minor Axis | 60 mm |
---|
Standards
CPR Euroclass | B2ca-s1,d,1,a1 |
---|
CENELEC Compliance | EN 50290-2-20 |
---|
Applicable Environmental and Other Programs
Environmental Space | Indoor - Euroclass B2ca |
---|
EU Directive 2000/53/EC (ELV) | Yes |
---|
EU Directive 2003/96/EC (BFR) | Yes |
---|
EU Directive 2011/65/EU (RoHS 2) | Yes |
---|
EU Directive 2012/19/EU (WEEE) | Yes |
---|
EU CE Mark | Yes |
---|
Suitability
Suitability - Indoor | Yes |
---|
Suitability - Non-Halogenated | Yes |
---|
Suitability - Sunlight Resistance | Yes |
---|
Flammability, LS0H, Toxicity Testing
IEC Flammability | IEC 60332-1-2 |
---|
IEC 60754-1 - Halogen Amount | Zero |
---|
IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity | 2.5 µS/mm |
---|
IEC 60754-2 - Halogen Acid Gas Amount - Min. pH | 4.3 |
---|
IEC 61034-2 - Smoke Density Min. Transmittance | 60% |
---|
History
Update and Revision | Revision Number: 0.26 Revision Date: 03-06-2023 |
---|
Documentation
Product Bulletins
Catalogs
Brochures
Data Sheets