Belden

8762ELW - Electronic, 2 C #20 Str TC, PE ins, OS, LSNH Jkt, 300V, Cca

(No reviews yet) Write a Review
SKU:
8762ELW
Shipping:
Calculated at Checkout
$0.00

Description

Electronic, 2 Conductor 20AWG (7x28) Tinned Copper, PE Insulation, Overall Beldfoil® Shield, LSZH Outer Jacket, Cca

Specifications

Specifications

Product Overview

Suitable ApplicationsInstrumentation and computer cable; For data transmission applications

Physical Characteristics (Overall)

Conductor

AWGStrandingMaterialNo. of Pairs
207x28TC - Tinned Copper1
Conductor Count2

Insulation

MaterialNominal DiameterDiameter +/- ToleranceNominal Wall Thickness
PE - Polyethylene1.78 mm0.05 mm0.016 in

Color Chart

NumberColor
Pair 1Black & Clear

Outer Shield

TypeMaterialMaterial Trade NameCoverage [%]Thickness of FoilDrainwire MaterialDrainwire AWGDrainwire Construction n x D
TapeBi-Laminate (Alum+Poly)Beldfoil® (Z-Fold®)100%9 / 12 µmTC - Tinned CopperAWG20/77x28

Outer Jacket

MaterialNominal DiameterNominal Wall Thickness
LSZH - Low Smoke Zero Halogen (Flame Retardant)5.4 mm0.9 mm

Construction and Dimensions

Stranding

Twists
6 twist/ft

Electrical Characteristics

Conductor DCR

Nominal Conductor DCR
31.2 Ohm/km

Capacitance

Nom. Capacitance Conductor to ConductorNom. Capacitance Conductor to Other Conductor to Shield
88.6 pF/m160.8 pF/m

Inductance

Nominal InductanceNominal Pair Inductance
0.18 µH/ft0.591 µH/m

Impedance

Nominal Characteristic Impedance
56 Ohm

Delay

Nominal Velocity of Propagation (VP) [%]
66%

Current

ElementMax. Recommended Current [A]
Conductor(s)3.9 Amps per Conductor

Voltage

Voltage Rating [V]
300 V

Temperature Range

Installation Temperature Range-15°C To +80°C
Storage Temperature Range-45°C To +80°C
Operating Temp Range (Flexible Install)-15°C To +80°C
Operating Temp Range (Fixed Install)-45°C To +80°C

Mechanical Characteristics

Oil ResistanceIEC 60811-404
Max. Pull Tension210 N
Min. Bend Radius During Installation54 mm
Min. Bend Radius/Minor Axis2 in

Standards

CPR EuroclassCca-s1,d1,a1
CENELEC ComplianceEN 50290-2-20

Applicable Environmental and Other Programs

Environmental SpaceIndoor/Outdoor - Euroclass Cca
EU Directive ComplianceEU Directive 2003/11/EC (BFR)
EU CE MarkYes
MII Order #39 (China RoHS)Yes

Suitability

Suitability - IndoorYes
Suitability - Non-HalogenatedYes
Suitability - Sunlight ResistanceYes

Flammability, LS0H, Toxicity Testing

IEC FlammabilityIEC 60332-1-2
IEC 60754-1 - Halogen AmountZero
IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity2.5 µS/mm
IEC 60754-2 - Halogen Acid Gas Amount - Min. pH4.3
IEC 61034-2 - Smoke Density Min. Transmittance60%

Plenum/Non-Plenum

Plenum (Y/N)No

History

Update and RevisionRevision Number: 0.27 Revision Date: 11-09-2022
View AllClose