Audio, Control & Instrument Cable, 22 AWG stranded (7x30) tinned copper conductor, FEP insulation, twisted pairs individually shielded with Beldfoil® (100% coverage), overall jacket per table below, 22 AWG stranded tinned copper drain wire.
Specifications
Specifications
Product Overview
Suitable Applications | extreme high temperature environments; chemical resistant; outdoor and burial applications; low voltage analog signals (4-20ma, 0-10v, ...); low voltage digital control (24v, …); line level audio; voice communications; panel wiring |
---|
Physical Characteristics (Overall)
Conductor
AWG | Stranding | Material | Nominal Diameter | No. of Pairs |
---|
22 | 7x30 | TC - Tinned Copper | 0.03 in | 3 |
Insulation
Material | Nominal Wall Thickness |
---|
FEP - Fluorinated Ethylene Propylene | 0.01 in |
Color Chart
Number | Color |
---|
1 | Black & Red |
2 | Black & White |
3 | Black & Green |
Inner Shield
Type | Material | Material Trade Name | Coverage [%] | Drainwire Material | Drainwire AWG | Drainwire Construction n x D |
---|
Tape | Bi-Laminate (Alum+Poly) | Beldfoil® (Z-Fold®) | 100% | TC - Tinned Copper | 22 | Stranded |
Outer Shield
Material | Drainwire AWG |
---|
No Shield | 22 |
Outer Jacket
Material | Nominal Diameter | Nominal Wall Thickness |
---|
PVDF - Polyvinylidene Fluoride | 0.234 in | 0.014 in |
Electrical Characteristics
Conductor DCR
Individual Pair Nominal Shield DCR | Max. Conductor DCR |
---|
11.3 Ohm/1000ft | 160 Ohm/km |
Capacitance
Nom. Capacitance Conductor to Conductor | Nom. Capacitance Conductor to Other Conductor to Shield |
---|
31 pF/ft | 67 pF/ft |
Inductance
Nominal Inductance |
---|
0.18 µH/ft |
Impedance
Nominal Characteristic Impedance |
---|
50 Ohm |
Delay
Max. Delay Skew | Nominal Delay | Nominal Velocity of Propagation (VP) [%] |
---|
69 ns/100m | 1.47 ns/ft | 69% |
Current
Max. Recommended Current [A] |
---|
3.5 Amps per Conductor at 25ºC |
Voltage
UL Voltage Rating |
---|
300 V RMS |
Temperature Range
Operating Temperature Range | -20°C To +150°C |
---|
Mechanical Characteristics
Bulk Cable Weight | 36 lbs/1000ft |
---|
Max. Pull Tension | 82 lbs |
---|
Min. Bend Radius/Minor Axis | 2.5 in |
---|
Standards
NEC/(UL) Compliance | CMP |
---|
CEC/C(UL) Compliance | CMP |
---|
Applicable Environmental and Other Programs
EU Directive 2000/53/EC (ELV) | Yes |
---|
EU Directive 2003/96/EC (BFR) | Yes |
---|
EU Directive 2011/65/EU (RoHS 2) | Yes |
---|
EU Directive 2012/19/EU (WEEE) | Yes |
---|
EU Directive Compliance | EU Directive 2003/11/EC (BFR) |
---|
EU CE Mark | Yes |
---|
MII Order #39 (China RoHS) | Yes |
---|
Flammability, LS0H, Toxicity Testing
UL Flammability | NFPA 262 Plenum Flame Test (UL910) |
---|
CSA Flammability | FT6 |
---|
UL voltage rating | 300 V RMS |
---|
Plenum/Non-Plenum
Related Part Numbers
Non-Plenum Number | 8777 |
---|
Footnote | C - CRATE REEL PUT-UP. |
---|