Audio, Control & Instrument, 6 Pair AWG 22 Tinned Copper - Stranded, Polyolefin (PO, PE, PP) insulation, Individually Foiled + No Overall shielding, LSZH / FRNC jacket , 300V
Specifications
Specifications
Product Overview
Suitable Applications | Instrumentation and computer cable; For data transmission applications |
---|
Physical Characteristics (Overall)
Conductor
AWG | Stranding | Material | No. of Pairs |
---|
22 | 7x30 | TC - Tinned Copper | 6 |
Insulation
Material | Nominal Diameter | Diameter +/- Tolerance |
---|
PP - Polypropylene | 1.27 mm | 0.05 mm |
Color Chart
Number | Color |
---|
Pair 1 | Black & Red |
Pair 2 | Black & White |
Pair 3 | Black & Green |
Pair 4 | Black & Blue |
Pair 5 | Black & Yellow |
Pair 6 | Black & Brown |
Table Notes | Shielded pairs |
---|
Color Chart 2
Number | Color |
---|
Pair 1 | Red |
Pair 2 | Green |
Pair 3 | Blue |
Pair 4 | Blue |
Pair 5 | Blue |
Pair 6 | Blue |
Inner Shield
Type | Layer | Material | Material Trade Name | Thickness of Foil | Drainwire Material | Drainwire AWG |
---|
Tape | 1 | Bi-Laminate (Alum+Poly) | Beldfoil® (Z-Fold®) | 9 / 12 µm | TC - Tinned Copper | AWG22/7 |
Tape | 2 | Polyester | | 12 µm | | |
Inner Jacket
Material | Color | Nominal Diameter | Nominal Wall Thickness |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | Chrome (RAL 7037) | 9.5 mm | 0.89 mm |
Outer Shield
Material |
---|
Bi-Laminate (Alum+Poly) |
Outer Jacket
Material | Nominal Diameter | Nominal Wall Thickness |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | 13.9 mm | 1.35 mm |
Construction and Dimensions
Cabling
Description | Filler |
---|
1 center filler and 6 pairs twisted to cable core covered with a polypropylene foil | Foamed flame retardant Polypropylene (2.50 mm) |
Armor
Type of Armor | Material | Thickness of Armoring Wires | Coverage Percentage |
---|
Steel Wire Armoring | Galvanized steel wire | 1.25 mm | Min. 95% |
Electrical Characteristics
Conductor DCR
Nominal Conductor DCR | Nominal Inner Shield DCR |
---|
49.2 Ohm/km | 34.8 Ohm/km |
Capacitance
Nom. Capacitance Conductor to Conductor | Nom. Capacitance Conductor to Other Conductor to Shield |
---|
98.4 pF/m | 180.4 pF/m |
Inductance
Nominal Pair Inductance |
---|
0.59 µH/m |
Impedance
Nominal Characteristic Impedance |
---|
50 Ohm |
Current
Element | Max. Recommended Current [A] |
---|
Conductor(s) | 2 A |
Voltage
Temperature Range
Installation Temperature Range | -15°C To +80°C |
---|
Storage Temperature Range | -45°C To +80°C |
---|
Operating Temp Range (Flexible Install) | -15°C To +80°C |
---|
Operating Temp Range (Fixed Install) | -45°C To +80°C |
---|
Mechanical Characteristics
Oil Resistance | IEC 60811-404 |
---|
Min. Bend Radius During Installation | 208.5 mm |
---|
Standards
CENELEC Compliance | EN 50290-2-20 |
---|
Applicable Environmental and Other Programs
Environmental Space | Indoor |
---|
Suitability
Suitability - Sunlight Resistance | Yes |
---|
Flammability, LS0H, Toxicity Testing
IEC Flammability | IEC 60332-3-24 |
---|
IEC 60754-1 - Halogen Amount | Zero |
---|
IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity | 2.5 µS/mm |
---|
IEC 60754-2 - Halogen Acid Gas Amount - Min. pH | 4.3 |
---|
IEC 61034-2 - Smoke Density Min. Transmittance | 60% |
---|
History
Update and Revision | Revision Number: 0.226 Revision Date: 11-09-2022 |
---|
Documentation
Product Bulletins
Data Sheets