Electronic, 2 Pair 18AWG (16x30) Tinned Copper, PVC Insulation, LSZH Outer Jacket, CMG
Specifications
Specifications
Construction Details
Conductor
| Element | Number of Element | Size | Stranding | Material |
|---|
| Pair(s) | 2 | 18 AWG | 16x30 | TC - Tinned Copper |
Insulation
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|
| Pair(s) | PP - Polypropylene | 0.013 in (0.33 mm) | 0.073 in (1.9 mm) | Black & Red, Black & White |
Outer Shield
Outer Jacket
| Material | Nom. Thickness | Nom. Diameter |
|---|
| LSZH - Low Smoke Zero Halogen (Flame Retardant) | 0.035 in (0.89 mm) | 0.333 in |
| Overall Cable Diameter (Nominal) | 0.333 in |
|---|
Electrical Characteristics
Electricals
| Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Max. Current |
|---|
| 7.2 Ohm/1000ft | 17.5 pF/ft (57.4 pF/m) | 11.2 Amps per Conductor at 30ºC |
Voltage
Mechanical Characteristics
Temperature
| UL Temperature | Operating |
|---|
| 75°C | -20°C to 75°C |
Bend Radius
| Stationary Min. | Installation Min. |
|---|
| 3.33 in (84.6 mm) | 3.33 in |
| Max. Pull Tension | 83.2 lbs (37.7 kg) |
|---|
| Bulk Cable Weight | 65 lbs/1000ft |
|---|
Standards and Compliance
| Environmental Suitability | Indoor |
|---|
| Flammability / Reaction to Fire | UL1685 FT4 Loading, FT4 |
|---|
| CPR Compliance | CPR Euroclass: Eca |
|---|
| NEC / UL Compliance | Article 800, CMG |
|---|
| AWM Compliance | AWM 21307 |
|---|
| CEC / C(UL) Compliance | CMG |
|---|
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
|---|
| UK Regulation Compliance | UKCA Mark |
|---|
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
|---|
History
| Update and Revision | Revision Number: 0.343 Revision Date: 05-05-2023 |
|---|
Documentation
Product Bulletins
Catalogs
Brochures
Compliance Documentation
Data Sheets