High Performance Instrumentation, 1 Pair 18AWG (19x30) Tinned Copper, PVC-NYL Insulation E2 Color Code, Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC
Specifications
Specifications
Product Overview
Suitable Applications | Industrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, …), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Pair(s) | 1 | 18 AWG | 19x30 | TC - Tinned Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Pair(s) | PVC/Nylon - Polyvinyl Chloride + Nylon | 0.022 in (0.56 mm) | 0.088 in (2.2 mm) | ICEA Chart E2 |
Outer Shield
Shield Type | Material | Coverage | Drainwire Type |
---|
Tape | Bi-Laminate (Alum+Poly) | 100% | 18 AWG (19x30) TC |
Outer Jacket
Separator | Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
Cotton Serve | PVC - Polyvinyl Chloride | 0.047 in (1.2 mm) | 0.274 in (6.96 mm) | Yes |
Overall Cable Diameter (Nominal) | 0.274 in (6.96 mm) |
---|
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Max. Current |
---|
Pair(s) | 7.06 Ohm/1000ft | 43 pF/ft (140 pF/m) | 74 pF/ft (240 pF/m) | 5 Amps per Conductor at 25ºC |
Voltage
UL Voltage Rating |
---|
600 V (TC), 150 V (NPLF) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
90°C Dry, 90°C Wet | -30°C to +90°C Dry, 75°C wet |
Bend Radius
Stationary Min. | Installation Min. |
---|
2.7 in (69 mm) | 2.7 in (69 mm) |
Max. Pull Tension | 74.1 lbs (33.6 kg) |
---|
Bulk Cable Weight | 40 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor/Outdoor, Indoor, Outdoor, Sunlight Resistance, Burial |
---|
Flammability / Reaction to Fire | UL 1685 UL Loading, IEEE 1202, FT4 |
---|
CPR Compliance | CPR Euroclass: Eca |
---|
NEC / UL Compliance | Article 336, Article 760, NPLF, TC |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
UK Regulation Compliance | UKCA Mark |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
History
Update and Revision | Revision Number: 0.540 Revision Date: 04-14-2023 |
---|
Documentation
Catalogs
Compliance Documentation
Data Sheets