High Performance Instrumentation, 11 Pair 18AWG (19x30) Tinned Copper, PVC Insulation E2 Color Code, Overall Beldfoil® Shield, PVC Outer Jacket, PLTC
Specifications
Specifications
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Pair(s) | 11 | 18 AWG | 19x30 | TC - Tinned Copper |
Insulation
Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
PVC - Polyvinyl Chloride | 0.017 in (0.43 mm) | 0.078 in (2.0 mm) | Black, Red and Numbered |
Outer Shield
Shield Type | Material | Coverage | Drainwire Type |
---|
Tape | Bi-Laminate (Alum+Poly) | 100% | 18 AWG (7x26) TC |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
PVC - Polyvinyl Chloride | 0.063 in (1.6 mm) | 0.682 in | Yes |
Electrical Characteristics
Electricals
Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Max. Current |
---|
7.19 Ohm/1000ft | 35 pF/ft (110 pF/m) | 54 pF/ft (180 pF/m) | 7 Amps per Conductor at 25ºC |
Voltage
UL Voltage Rating |
---|
300 V (PLTC) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
105°C | -30°C To +105°C |
Max. Pull Tension | 565.8 lbs (256.6 kg) |
---|
Bulk Cable Weight | 250 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial |
---|
Flammability / Reaction to Fire | UL 1685 FT4 loading, FT4, T-29-520, IEEE 1202 FT4 |
---|
NEC / UL Compliance | Article 725, Article 727, Article 800 |
---|
AWM Compliance | AWM 2464 |
---|
CEC / C(UL) Compliance | CMG |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
History
Update and Revision | Revision Number: 0.418 Revision Date: 12-16-2022 |
---|
Documentation
Product Bulletins
Catalogs
Compliance Documentation
Data Sheets