Electronic, 2 Conductor 18AWG (Solid) Bare Copper, PVC Insulation, Red PVC Outer Jacket, FPLR
Specifications
Specifications
Product Overview
Suitable Applications | fire alarms; indoor applications; low voltage analog signals (4-20ma, 0-10v, ...); low voltage control (24v, …) |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 2 | 18 AWG | Solid | BC - Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Conductor(s) | PVC - Polyvinyl Chloride | 0.017 in (0.43 mm) | 0.072 in mm | Black, Red |
Outer Shield
Outer Jacket
Material | Nom. Thickness | Nom. Diameter |
---|
PVC - Polyvinyl Chloride | 0.037 in (0.94 mm) | 0.228 in |
Overall Cable Diameter (Nominal) | 0.228 in |
---|
Electrical Characteristics
Electricals
Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Max. Current |
---|
6.3 Ohm/1000ft | 22 pF/ft (72 pF/m) | 5.2 Amps per Conductor at 25ºC |
Voltage
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
105°C | -40°C To +105°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
2.28 in (57.9 mm) | 2.28 in |
Max. Pull Tension | 39.2 lbs (17.8 kg) |
---|
Bulk Cable Weight | 26 lbs/1000ft |
---|
Standards and Compliance
Flammability / Reaction to Fire | UL 1666 riser, FT4 |
---|
CPR Compliance | CPR Euroclass: Eca |
---|
NEC / UL Compliance | Article 760, Article 800, CMR, FPLR |
---|
AWM Compliance | AWM 2464 |
---|
CEC / C(UL) Compliance | FAS105 |
---|
European Directive Compliance | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
UK Regulation Compliance | UKCA Mark |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
History
Update and Revision | Revision Number: 0.390 Revision Date: 05-05-2023 |
---|
Documentation
Product Bulletins
Compliance Documentation
Data Sheets