RS-232/422, 2 Pair AWG 24 Tinned Copper - Stranded, Polyolefin (PO, PE, PP) insulation, Individually Foiled + No Overall shielding, LSZH / FRNC jacket , 300V, SWA
Specifications
Specifications
Product Overview
Suitable Applications | Instrumentation and computer cable; For data transmission applications |
---|
Physical Characteristics (Overall)
Conductor
AWG | Stranding | Material | No. of Pairs |
---|
24 | 7x32 | TC - Tinned Copper | 2 |
Insulation
Material | Material Trade Name | Nominal Diameter | Diameter +/- Tolerance |
---|
PE - Polyethylene (Foam) | Datalene® | 1.55 mm | 0.06 mm |
Color Chart
Number | Color |
---|
Pair 1 | Black & Red |
Pair 2 | Black & White |
Table Notes | Shielded pairs |
---|
Color Chart 2
Number | Color |
---|
Pair 1 | Red |
Pair 2 | Green |
Inner Shield
Type | Material | Material Trade Name | Thickness of Foil | Drainwire Material | Drainwire AWG |
---|
Tape | Bi-Laminate (Alum+Poly) | Beldfoil® (Z-Fold®) | 9 / 12 µm | TC - Tinned Copper | AWG24/7 |
Inner Jacket
Material | Color | Nominal Diameter | Min. Wall Thickness | Min. Average Wall Thickness |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | Chrome (RAL 7037) | 7.9 mm | 0.91 mm | 1.10 mm |
Outer Shield
Material |
---|
Bi-Laminate (Alum+Poly) |
Outer Jacket
Material | Nominal Diameter | Min. Wall Thickness | Nominal Wall Thickness |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | 12.5 mm | 1.25 mm | 1.35 mm |
Construction and Dimensions
Cabling
Description | Filler |
---|
2 pairs and 2 fillers twisted to cable core | Polypropylene (Blue, 2.20 mm) |
Armor
Type of Armor | Material | Thickness of Armoring Wires | Coverage Percentage |
---|
Steel Wire Armoring | Galvanized steel wire | 0.9 mm | Min. 95% |
Electrical Characteristics
Conductor DCR
Nominal Conductor DCR | Nominal Inner Shield DCR |
---|
78.7 Ohm/km | 59.1 Ohm/km |
Capacitance
Nom. Capacitance Conductor to Conductor | Nom. Capacitance Conductor to Other Conductor to Shield |
---|
41 pF/m | 76.1 pF/m |
Inductance
Nominal Pair Inductance |
---|
0.49 µH/m |
Impedance
Nominal Characteristic Impedance |
---|
100 Ohm |
High Frequency (Nominal/Typical)
Frequency [MHz] | Nom. Insertion Loss |
---|
2 MHz | 4.63 dB/100m |
3 MHz | 5.35 dB/100m |
4 MHz | 5.91 dB/100m |
5 MHz | 6.5 dB/100m |
6 MHz | 6.89 dB/100m |
11 MHz | 9.15 dB/100m |
12 MHz | 9.51 dB/100m |
24 MHz | 13.16 dB/100m |
Current
Element | Max. Recommended Current [A] |
---|
Conductor(s) | 1 A |
Voltage
Temperature Range
Installation Temperature Range | -15°C To +80°C |
---|
Storage Temperature Range | -45°C To +80°C |
---|
Operating Temp Range (Flexible Install) | -15°C To +80°C |
---|
Operating Temp Range (Fixed Install) | -45°C To +80°C |
---|
Mechanical Characteristics
Oil Resistance | IEC 60811-404 |
---|
Min. Bend Radius During Installation | 187.5 mm |
---|
Standards
CENELEC Compliance | EN 50290-2-20 |
---|
Applicable Environmental and Other Programs
Environmental Space | Indoor |
---|
Suitability
Suitability - Sunlight Resistance | Yes |
---|
Flammability, LS0H, Toxicity Testing
IEC Flammability | IEC 60332-3-24 |
---|
IEC 60754-1 - Halogen Amount | Zero |
---|
IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity | 2.5 µS/mm |
---|
IEC 60754-2 - Halogen Acid Gas Amount - Min. pH | 4.3 |
---|
IEC 61034-2 - Smoke Density Min. Transmittance | 60% |
---|
History
Update and Revision | Revision Number: 0.231 Revision Date: 11-09-2022 |
---|
Documentation
Product Bulletins
Data Sheets