Computer EIA RS-232/422 Cable, 3-Pair, 24 AWG stranded (7x32) tinned copper conductors, polyethylene insulation, overall Beldfoil® (100% coverage) + tinned copper braid shield (65% coverage), 24 AWG stranded tinned copper drain wire, PVC jacket.
Specifications
Specifications
Product Overview
Suitable Applications | RS-232 extended distance applications; RS-422 applications; computer communications; low voltage analog signals (4-20ma, 0-10v, ...); low voltage digital control (24v, …); line level audio; panel wiring |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Pair(s) | 3 | 24 AWG | 7x32 | TC - Tinned Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Pair(s) | PE - Polyethylene | 0.0155 in (0.394 mm) | 0.054 in (1.4 mm) | Western Electric Standard |
Outer Shield
Shield Type | Material | Coverage | Drainwire Type |
---|
Tape | Bi-Laminate (Alum+Poly) | 100% | 24 AWG (7x32) TC |
Braid | Tinned Copper (TC) | 65% | |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter |
---|
PVC - Polyvinyl Chloride | 0.035 in (0.89 mm) | 0.305 in (7.75 mm) |
Overall Cable Diameter (Nominal) | 0.305 in (7.75 mm) |
---|
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
---|
Pair(s) | 28.8 Ohm/1000ft | 15.5 pF/ft (50.9 pF/m) | 27.5 pF/ft (90.2 pF/m) | 100 Ohm | 66% | 2.1 Amps per Conductor at 25ºC |
Voltage
UL Voltage Rating |
---|
300 V (CM), 30 V (AWM 2919) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
80°C | -30°C to +80°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
3 in (76 mm) | 3 in (76 mm) |
Max. Pull Tension | 65 lbs (29 kg) |
---|
Bulk Cable Weight | 48 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor |
---|
Flammability / Reaction to Fire | UL 1685 FT4 Loading, IEC 60332-1-2 |
---|
CPR Compliance | CPR Euroclass: Eca |
---|
NEC / UL Compliance | Article 800, CM |
---|
AWM Compliance | AWM 2919 |
---|
CEC / C(UL) Compliance | CM |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
UK Regulation Compliance | UKCA Mark |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
History
Update and Revision | Revision Number: 0.479 Revision Date: 01-20-2023 |
---|
Documentation
Product Bulletins
Catalogs
Brochures
Compliance Documentation
Data Sheets