RS-485, 4 Pair AWG 24 Tinned Copper - Stranded, Polyolefin (PO, PE, PP) insulation, Foil + Braid(s) shielding, LSZH / FRNC jacket , 300V, SWA
Specifications
Specifications
Product Overview
Suitable Applications | RS-485, POS; Computer communications; Low Voltage Analog Signals (4-20ma, 0-10v, ...); Low Voltage Digital Control (24v, …); Line Level Audio; Panel Wiring; serial communication (RS-485 standard) comprising of PLCs, VFDs, HMIs, motors, RTU, SCADA, etc. within noisy environments over long distance, etc. |
---|
Physical Characteristics (Overall)
Conductor
AWG | Stranding | Material | No. of Pairs |
---|
24 | 7x32 | TC - Tinned Copper | 4 |
Conductor Count | 8 |
---|
Total Number of Pairs | 4 |
---|
Insulation
Material | Nominal Diameter | Diameter +/- Tolerance |
---|
PE - Polyethylene | 1.73 mm | 0.05 mm |
Color Chart
Number | Color |
---|
Pair 1 | White/Blue & Blue/White |
Pair 2 | White/Orange & Orange/White |
Pair 3 | White/Green & Green/White |
Pair 4 | White/Brown & Brown/White |
Inner Jacket
Material | Color | Nominal Diameter | Nominal Wall Thickness |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | Chrome (RAL 7037) | 9.9 mm | 0.89 mm |
Outer Shield
Type | Material | Material Trade Name | Coverage [%] | Drainwire Material | Drainwire AWG |
---|
Tape | | Beldfoil® (Z-Fold®) | 100% | TC - Tinned Copper | AWG 24/7 |
Braid | Tinned Copper (TC) | | 90% | | |
Outer Jacket
Material | Nominal Diameter | Nominal Wall Thickness |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | 15.1 mm | 1.35 mm |
Construction and Dimensions
Cabling
Description |
---|
4 pairs twisted to cable core |
Armor
Type of Armor | Material | Thickness of Armoring Wires | Coverage Percentage |
---|
Steel Wire Armoring | Galvanized steel wire | 1.25 mm | Min. 95% |
Electrical Characteristics
Conductor DCR
Nominal Conductor DCR | Nominal Outer Shield DCR |
---|
78.7 Ohm/km | 6.9 Ohm/km |
Capacitance
Nom. Capacitance Conductor to Conductor | Nom. Capacitance Conductor to Other Conductor to Shield |
---|
42 pF/m | 75.5 pF/m |
Impedance
Frequency [MHz] | Nominal Characteristic Impedance |
---|
1 MHz | 120 Ohm |
High Frequency (Nominal/Typical)
Frequency [MHz] | Nom. Insertion Loss |
---|
1 MHz | 1.97 dB/100m |
Delay
Nominal Delay | Nominal Velocity of Propagation (VP) [%] |
---|
520 ns/ft | 66% |
Current
Element | Max. Recommended Current [A] |
---|
Conductor(s) | 2.1 Amps per Conductor |
Voltage
Temperature Range
Installation Temperature Range | -15°C To +80°C |
---|
Storage Temperature Range | -45°C To +80°C |
---|
Operating Temp Range (Flexible Install) | -15°C To +80°C |
---|
Operating Temp Range (Fixed Install) | -45°C To +80°C |
---|
Mechanical Characteristics
Oil Resistance | IEC 60811-404 |
---|
Max. Pull Tension | 500 N |
---|
Min. Bend Radius During Installation | 151 mm |
---|
Standards
CENELEC Compliance | EN 50290-2-20 |
---|
Applicable Environmental and Other Programs
Environmental Space | Indoor/Outdoor |
---|
EU CE Mark | Yes |
---|
Suitability
Suitability - Indoor | Yes |
---|
Suitability - Non-Halogenated | Yes |
---|
Suitability - Oil Resistance | Yes |
---|
Suitability - Outdoor | Yes |
---|
Suitability - Sunlight Resistance | Yes |
---|
Flammability, LS0H, Toxicity Testing
IEC Flammability | IEC 60332-3-24 |
---|
IEC 60754-1 - Halogen Amount | Zero |
---|
IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity | 2.5 µS/mm |
---|
IEC 60754-2 - Halogen Acid Gas Amount - Min. pH | 4.3 |
---|
IEC 61034-2 - Smoke Density Min. Transmittance | 60% |
---|
History
Update and Revision | Revision Number: 0.219 Revision Date: 11-09-2022 |
---|
Documentation
Product Bulletins
Catalogs
Guides
Line Cards
Data Sheets