Belden

A03042G - TC VN/PVC, 3+G C #4+8 Str BC, PVC-NYL Ins E2, Blk PVC Jkt, 600V TC-ER 90C Dry 75C Wet SUN RES DIR BUR

(No reviews yet) Write a Review
SKU:
A03042G
Shipping:
Calculated at Checkout
$0.00

Description

UL Type TC-ER (1277) PVC-Nylon/PVC, 3+G Conductor 4+8AWG (7x12+7x16) Bare Copper, PVC-NYL Insulation E2 Color Code, Black PVC Outer Jacket, 600V TC-ER 90C Dry 75C Wet SUN RES DIR BUR

Specifications

Specifications

Put-Up TypeReel

Physical Characteristics (Overall)

Conductor

ElementAWGStrandingMaterialNo. of Conductors
Conductor(s)47x12BC - Bare Copper3
Ground87x16BC - Bare Copper1
Conductor Count3

Insulation

MaterialNominal DiameterNominal Wall Thickness
PVC/Nylon - Polyvinyl Chloride + Nylon0.0309 in0.0485 in
No Insulation

Color Chart

NumberColor
1Black
2Red
3Blue

Outer Jacket

MaterialNominal DiameterNominal Wall Thickness
PVC - Polyvinyl Chloride0.822 in0.063 in

Electrical Characteristics

Conductor DCR

Nominal Conductor DCR
0.26 Ohm/1000ft

Current

Max. Recommended Current [A]
95 Amps per Conductor at 30ºC

Voltage

UL DescriptionUL Voltage RatingVoltage Rating [V]
TC-ER600 V RMS (Type TC)600 V RMS (Type TC)

Temperature Range

Operating Temperature Range-30°C to 90°C Dry, +75°C Wet

Mechanical Characteristics

Bulk Cable Weight548 lbs/1000ft
Max. Pull Tension1002 lbs
Min. Bend Radius/Minor Axis3.29 in

Standards

NEC/(UL) ComplianceTC-ER, THWN-2 Singles

Applicable Environmental and Other Programs

EU Directive 2000/53/EC (ELV)Yes
EU Directive 2011/65/EU (RoHS 2)Yes
EU Directive 2012/19/EU (WEEE)Yes
EU Directive ComplianceEU Directive 2003/11/EC (BFR)

Suitability

Suitability - BurialYes
Suitability - IndoorYes
Suitability - OutdoorYes
Suitability - Sunlight ResistanceYes

Flammability, LS0H, Toxicity Testing

UL FlammabilityUL1685 UL Loading
IEEE Flammability1202
UL voltage rating600 V RMS (Type TC)

History

Update and RevisionRevision Number: 0.46 Revision Date: 04-14-2023
View AllClose