UL Type TC (1277) PVC-Nylon/PVC, 4 Conductor 16AWG (7x24) Bare Copper, PVC-NYL Insulation E2 Color Code, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR
Specifications
Specifications
Product Overview
Suitable Applications | Power and Control Applications up to 600V |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 4 | 16 AWG | 7x24 | BC - Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Conductor(s) | PVC/Nylon - Polyvinyl Chloride + Nylon | 0.020 in (0.51 mm) | 0.099 in (2.5 mm) | ICEA Chart E2 |
Outer Shield
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
PVC - Polyvinyl Chloride | 0.047 in (1.2 mm) | 0.331 in | Yes |
Overall Cable Diameter (Nominal) | 0.331 in |
---|
Electrical Characteristics
Electricals
Nom. Conductor DCR | Max. Current |
---|
4.45 Ohm/1000ft | 14.4 Amps per Conductor at 30ºC |
Voltage
UL Voltage Rating |
---|
600 V (TC-ER), 150 V (NPLF) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|
90°C Dry, 90°C Wet | -30°C To +90°C Wet/90°C Dry |
Bend Radius
Stationary Min. | Installation Min. |
---|
1.32 in (33.5 mm) | 1.65 in |
Max. Pull Tension | 142.8 lbs (64.77 kg) |
---|
Bulk Cable Weight | 72 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial |
---|
Sustainability | CA Prop 65 |
---|
Flammability / Reaction to Fire | UL 1685 UL Loading, IEEE 1202 FT4 |
---|
NEC / UL Compliance | Article 336, Article 400, Article 760, TC-ER, NPLF, TFFN |
---|
European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
History