UL Type TC (1277) PVC-Nylon/PVC, 40 Conductor 14AWG (7x22) Bare Copper, PVC-NYL Insulation E2 Color Code, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

Specifications

Specifications

Put-Up TypeReel

Physical Characteristics (Overall)

Conductor

ElementAWGStrandingMaterialNo. of Conductors
Conductor(s)147x22BC - Bare Copper40
Conductor Count40

Insulation

MaterialNominal Diameter
PVC/Nylon - Polyvinyl Chloride + Nylon0.112 in

Color Chart

NumberColor
1Black
2Red
3Blue
4Orange
5Yellow
6Brown
7Red/Black
8Blue/Black
9Orange/Black
10Yellow/Black
11Brown/Black
12Black/Red
13Blue/Red
14Orange/Red
15Yellow/Red
16Brown/Red
17Black/Blue
18Red/Blue
19Orange/Blue
20Yellow/Blue
21Brown/Blue
22Black/Orange
23Red/Orange
24Blue/Orange
25Yellow/Orange
26Brown/Yellow
27Black/Yellow
28Red/Yellow
29Blue/Yellow
30Orange/Yellow
31Brown/Yellow
32Black/Brown
33Red/Brown
34Blue/Brown
35Orange/Brown
36Yellow/Brown
37Black
38Red
39Blue
40Orange

Outer Jacket

MaterialNominal DiameterNominal Wall Thickness
PVC - Polyvinyl Chloride0.985 in0.083 in

Electrical Characteristics

Conductor DCR

Nominal Conductor DCR
4.2 Ohm/1000ft

Current

Max. Recommended Current [A]
3.2 Amps per Conductor at 30ºC

Voltage

UL Voltage RatingVoltage Rating [V]
600 V RMS (Type TC)600 V RMS (Type TC)

Temperature Range

UL Temp Rating90°C Dry, 75°C Wet
Operating Temperature Range-25°C To +90°C

Mechanical Characteristics

UV ResistanceYes
Min Bend Radius (Overall)7.9 in
Min. Bend Radius/Minor Axis3.94 in

Standards

NEC/(UL) ComplianceTC-ER

Applicable Environmental and Other Programs

EU Directive 2000/53/EC (ELV)Yes
EU Directive 2011/65/EU (RoHS 2)Yes
EU Directive 2012/19/EU (WEEE)Yes
EU Directive 2015/863/EU (RoHS 2 amendment)Yes
EU Directive ComplianceEU Directive 2003/11/EC (BFR)
EU CE MarkYes

Suitability

Suitability - BurialYes
Suitability - IndoorYes
Suitability - OutdoorYes
Suitability - Sunlight ResistanceYes

Flammability, LS0H, Toxicity Testing

UL FlammabilityUL1685 Vertical Tray Flame Test
IEEE Flammability1202
UL voltage rating600 V RMS (Type TC)

History

Update and RevisionRevision Number: 0.50 Revision Date: 04-08-2022