Teck90 1000V, 3+G Conductor 6 AWG (7x14H) Bare Copper, XLPE insulation, 8 AWG (7x16H) bare copper ground wire, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, CSA SUN RES -40C
Specifications
Specifications
Product Overview
| Suitable Applications | Power and Control Applications up to 600V |
|---|
Construction Details
Conductor
| Element | Number of Element | Size | Stranding | Material |
|---|
| Conductor(s) | 3 | 6 | 7x14 | BC - Bare Copper |
| Ground | 1 | 8 | 7x16 | BC - Bare Copper |
Insulation
| Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|
| XLP, XLPO, XLPE (Thermoset) | 0.061 in (1.5 mm) | 0.300 in (7.62 mm) | Black, Red, Blue |
Inner Jacket
| Material | Nom. Thickness | Nom. Diameter |
|---|
| PVC - Polyvinyl Chloride | 0.063 in (1.6 mm) | 0.773 in (19.6 mm) |
Armor
| Armor Type & Material | Diameter Over Armor |
|---|
| AIA - Aluminum Interlock Armor | 1.033 in (26.24 mm) |
Outer Jacket
| Material | Nom. Thickness | Nom. Diameter | Ripcord |
|---|
| PVC - Polyvinyl Chloride | 0.048 in (1.2 mm) | 1.129 in (28.68 mm) | Yes |
Electrical Characteristics
Electricals
| Element | Nom. Conductor DCR | Max. Current |
|---|
| Conductor(s) | 0.41 Ohm/1000ft | 75 Amps per Conductor at 30ºC |
| Ground | 0.654 Ohm/1000ft (2.15 Ohm/km) | |
Voltage
| Voltage Rating |
|---|
| 1000 V (TECK 90) |
Mechanical Characteristics
Temperature
| UL Temperature | Operating | Installation |
|---|
| 90°C | -40°C To +90°C | -25°C To +90°C |
Bend Radius
| Stationary Min. | Installation Min. |
|---|
| 9.032 in (229.4 mm) | 9.032 in (229.4 mm) |
| Max. Pull Tension | 1462.1 lbs (663.20 kg) |
|---|
| Bulk Cable Weight | 687 lbs/1000ft |
|---|
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial |
|---|
| CEC / C(UL) Compliance | TECK 90, HL |
|---|
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
|---|
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
|---|
History
| Update and Revision | Revision Number: 0.196 Revision Date: 04-28-2023 |
|---|