Teck90 1000V, 4+G Conductor 2+6AWG (7x10H) Bare Copper, XLPE Insulation M4 Color Code, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, CSA HL SUN RES -40C
Specifications
Specifications
Product Overview
| Suitable Applications | Power and Control Applications up to 600V |
|---|
Construction Details
Conductor
| Element | Number of Element | Size | Stranding | Material |
|---|
| Conductor(s) | 4 | 2 AWG | 7x10 | BC - Bare Copper |
| Ground Wire | 1 | 6 AWG | 7x14 | BC - Bare Copper |
Insulation
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|
| Conductor(s) | XLP, XLPO, XLPE (Thermoset) | 0.06 in (1.5 mm) | 0.405 in mm | Red, Black, Blue, White |
| Ground Wire | No Insulation | | | |
Outer Shield
Inner Jacket
| Material | Nom. Thickness | Nom. Diameter |
|---|
| PVC - Polyvinyl Chloride | 0.083 in (2.1 mm) | 1.155 in (29.34 mm) |
Armor
| Armor Type & Material | Diameter Over Armor |
|---|
| AIA - Aluminum Interlock Armor | 1.415 in (35.94 mm) |
Outer Jacket
| Material | Nom. Thickness | Nom. Diameter | Ripcord |
|---|
| PVC - Polyvinyl Chloride | 0.053 in (1.3 mm) | 1.521 in | Yes |
| Overall Cable Diameter (Nominal) | 1.521 in |
|---|
Electrical Characteristics
Electricals
| Element | Nom. Conductor DCR | Max. Current |
|---|
| Conductor(s) | 0.166 Ohm/1000ft | 104 Amps per Conductor at 30ºC |
| Ground Wire | 0.419 Ohm/1000ft (1.37 Ohm/km) | |
Voltage
| Voltage Rating |
|---|
| 1000 V (TECK 90) |
Mechanical Characteristics
Temperature
| Operating | Installation |
|---|
| -40°C To +90°C | -25°C To +90°C |
Bend Radius
| Stationary Min. | Installation Min. |
|---|
| 12.09 in (307.1 mm) | 12.09 in |
| Max. Pull Tension | 3746.3 lbs (1699.3 kg) |
|---|
| Bulk Cable Weight | 1556 lbs/1000ft |
|---|
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial |
|---|
| CEC / C(UL) Compliance | TECK 90, HL |
|---|
| European Directive Compliance | EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
|---|
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
|---|
History
| Update and Revision | Revision Number: 0.233 Revision Date: 12-20-2022 |
|---|
Documentation
Catalogs
Technical Resources
Videos
Compliance Documentation
Data Sheets