Teck90 1000V, 2+G Conductor 10+12AWG (7x18H) Bare Copper, XLPE Insulation M4 Color Code, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, CSA HL SUN RES -40C
Specifications
Specifications
Product Overview
Suitable Applications | CEC Power and Control Applications up to 600V |
---|
Construction Details
Conductor
Element | Number of Element | Size | Stranding | Material |
---|
Conductor(s) | 2 | 10 AWG | 7x18 | BC - Bare Copper |
Ground Wire | 1 | 12 AWG | 7x20 | BC - Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|
Conductor(s) | XLP, XLPO, XLPE (Thermoset) | 0.045 in (1.1 mm) | 0.204 in mm | Black, White |
Ground Wire | No Insulation | | | |
Outer Shield
Inner Jacket
Material | Nom. Thickness | Nom. Diameter |
---|
PVC - Polyvinyl Chloride | 0.047 in (1.2 mm) | 0.502 in (12.8 mm) |
Armor
Armor Type & Material | Diameter Over Armor |
---|
AIA - Aluminum Interlock Armor | 0.727 in (18.5 mm) |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|
PVC - Polyvinyl Chloride | 0.048 in (1.2 mm) | 0.823 in (20.9 mm) | Yes |
Overall Cable Diameter (Nominal) | 0.823 in (20.9 mm) |
---|
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Max. Current |
---|
Conductor(s) | 1.06 Ohm/1000ft | 24 Amps per Conductor at 30ºC |
Ground Wire | 1.68 Ohm/1000ft (5.51 Ohm/km) | |
Voltage
Voltage Rating |
---|
1000 V (TECK 90) |
Mechanical Characteristics
Temperature
Operating | Installation |
---|
-40°C To +90°C | -25°C To +90°C |
Bend Radius
Stationary Min. | Installation Min. |
---|
6.58 in (167 mm) | 6.58 in (167 mm) |
Max. Pull Tension | 550.4 lbs (249.7 kg) |
---|
Bulk Cable Weight | 303 lbs/1000ft |
---|
Standards and Compliance
Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial |
---|
CEC / C(UL) Compliance | TECK 90, HL |
---|
European Directive Compliance | EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
---|
APAC Compliance | China RoHS II (GB/T 26572-2011) |
---|
History
Update and Revision | Revision Number: 0.247 Revision Date: 01-20-2023 |
---|
Documentation
Catalogs
Technical Resources
Videos
Compliance Documentation
Data Sheets