Outdoor (PUR jacket) optical fiber Central Loose Tube (jelly filled tube) cable with glass yarns as strength member and polyurethane outer jacket. Existing out of 1 Tube with a diameter of 3.3mm with 2 fibers MM OM4.
Specifications
Specifications
Product Overview
| Environmental Space | Indoor/Outdoor |
|---|
| Suitable Applications | For outdoor and indoor use in structured (data) wiring systems such as industrial backbone, campus backbone, building backbone (riser) and/or horizontal cabling. For outdoor and indoor use in networks for industrial, telecom, cable TV and/or broadcast. Easy to install in ducts, tunnels and/or tubes. |
|---|
Construction
Fiber Cable Construction
| Fiber Type | Fiber Count | Subunit Color |
|---|
| OM4 | 2 | TIA coding (Gxxxxxx.T): Natural |
| Fiber Color Coding | TIA coding (Gxxxxxx.T): Blue, Orange |
|---|
| Cable Core Water Tight | Yes |
|---|
| Cable Core Waterblocking | Waterblocking Glass Yarns + Tape |
|---|
| Bulk Cable Weight | 40 kg/km |
|---|
SubUnit Specifications
| Number of Active Subunits | 1 |
|---|
| Number of Subunit Positions | 1 |
|---|
| Fibers Per Subunit | 2 |
|---|
Jacket Specifications
| Number of Jackets | Single Jacket |
|---|
| Type of Armor | Non-Armored |
|---|
Outer Jacket Specifications
Outer Jacket
| Material | Nominal Diameter | Ripcord |
|---|
| PUR - Polyurethane | 6.3 mm | No |
Optical Characteristics
| Max. Attenuation at 1300 nm | 0.9 dB/km |
|---|
| Max. Attenuation at 850 nm | 2.9 dB/km |
|---|
Mechanical Characteristics
Mechanical Tests
| Description | Tested Standard | Requirement/Value | According to Family Specification |
|---|
| Cable Min. Bend Radius Installation (Short Term) | IEC 60794-1-21-E6 | 94.5 mm | IEC 60794-2-20 |
| Cable Min. Bend Radius Operation (Long Term) | IEC 60794-1-21-E11 | 63 mm | IEC 60794-2-20 |
| Cable Max. Tensile Strength Installation (Short Term) | IEC 60794-1-21-E1 | 1500 N (337 lbf) | IEC 60794-2-20 |
| Cable Max. Tensile Strength Operation (Long Term) | IEC 60794-1-21-E1 | 500 N (112 lbf) | IEC 60794-2-20 |
| Cable Max. Crush Resistance Installation (Short Term) | IEC 60794-1-21-E3 | 15 kN/m | IEC 60794-2-20 |
| Cable Max. Crush Resistance Operation (Long Term) | IEC 60794-1-21-E3 | 7.5 kN/m | IEC 60794-2-20 |
Temperature Range
| Operating Temperature Range | -30 °C to +70 °C |
|---|
| Installation Temperature Range | -5 °C to +50 °C |
|---|
| Storage Temperature Range | -30 °C to +70 °C |
|---|
Standards
| UL Rating/Flame Test | Non-UL Rated |
|---|
| REACH | Compliant |
|---|
| ISO/IEC Compliance | IEC 60794 |
|---|
| UV/ Sunlight Protection | Yes |
|---|
History
| Update and Revision | Revision Number: 0.44 Revision Date: 01-20-2023 |
|---|
Documentation
Product Bulletins
Catalogs
Warranties