Universal (Indoor/Outdoor) tight buffered with Steel Wire Armouring breakout cable with Low Smoke Zero Halogen outer jacket. 2 fibers MM OM3.
Specifications
Specifications
Product Overview
Environmental Space | Indoor/Outdoor |
---|
Suitable Applications | For outdoor and indoor use in structured (data) wiring systems such as industrial backbone, campus backbone, building backbone (riser) and/or horizontal cabling. For outdoor and indoor use in networks for industrial, telecom, cable TV and/or broadcast. Support all computer network applications such as FDDI, Gigabit Ethernet and ATM. |
---|
Construction
Fiber Cable Construction
Fiber Type | Fiber Count | Subunit Color |
---|
OM3 | 2 | Aqua |
Fiber Color Coding | TIA coding (Gxxxxxx.T): Blue |
---|
Buffer Specification
Fiber Type | Buffer Construction | Buffer Material | Buffer Diameter |
---|
OM3 | Tight | LSZH - Low Smoke Zero Halogen (Flame Retardant) | 0.9 mm |
Central Strength Member | GRP |
---|
Cable Core Water Tight | Yes |
---|
Cable Core Waterblocking | Waterblock Tape |
---|
Bulk Cable Weight | 325 kg/km |
---|
SubUnit Specifications
Number of Active Subunits | 2 |
---|
Number of Subunit Positions | 4 |
---|
Fibers Per Subunit | 1 |
---|
Jacket Specifications
Number of Jackets | Double Jacket |
---|
Type of Armor | Steel Wire |
---|
Inner Jacket
Color | Aqua |
---|
Nom. Diameter | 2.1 mm |
---|
Material | LSZH - Low Smoke Zero Halogen (Flame Retardant) |
---|
Outer Jacket Specifications
Outer Jacket
Material | Nominal Diameter | Ripcord |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | 11.6 mm | Yes |
Table Notes | Standard color: Black. Available colors: Orange, Yellow, Turquoise, Erika Violet, Red, Blue, Green, Brown, Violet, Pink, Grey, White, Black, Lime Green |
---|
Optical Characteristics
Max. Attenuation at 1300 nm | 0.9 dB/km |
---|
Max. Attenuation at 850 nm | 2.9 dB/km |
---|
Mechanical Characteristics
Mechanical Tests
Description | Tested Standard | Requirement/Value | According to Family Specification |
---|
Cable Min. Bend Radius Installation (Short Term) | IEC 60794-1-21-E6 | 232 mm | IEC 60794-2-20 |
Cable Min. Bend Radius Operation (Long Term) | IEC 60794-1-21-E11 | 116 mm | IEC 60794-2-20 |
Cable Max. Tensile Strength Installation (Short Term) | IEC 60794-1-21-E1 | 3750 N (843 lbf) | IEC 60794-2-20 |
Cable Max. Tensile Strength Operation (Long Term) | IEC 60794-1-21-E1 | 1250 N (281 lbf) | IEC 60794-2-20 |
Cable Max. Crush Resistance Installation (Short Term) | IEC 60794-1-21-E3 | 22 kN/m | IEC 60794-2-20 |
Cable Max. Crush Resistance Operation (Long Term) | IEC 60794-1-21-E3 | 11 kN/m | IEC 60794-2-20 |
Temperature Range
Operating Temperature Range | -30 °C to +70 °C |
---|
Installation Temperature Range | -5 °C to +50 °C |
---|
Storage Temperature Range | -30 °C to +70 °C |
---|
Standards
UL Rating/Flame Test | Non-UL Rated |
---|
IEC Flammability | IEC 60332-1-2 |
---|
IEC 60754-1 - Halogen Amount | Zero |
---|
IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity | 10 µS/mm |
---|
IEC 60754-2 - Halogen Acid Gas Amount - Min. pH | 4.3 |
---|
REACH | Compliant |
---|
ISO/IEC Compliance | IEC 60794 |
---|
UV/ Sunlight Protection | Yes |
---|
History
Update and Revision | Revision Number: 0.27 Revision Date: 02-09-2023 |
---|
Documentation
Catalogs
Flyers
Technical Resources
White Papers
Training
Warranties
Data Sheets