Description

Universal (Indoor/Outdoor) tight buffered with Steel Wire Armouring breakout cable with Low Smoke Zero Halogen outer jacket. 2 fibers MM OM4.

Specifications

Specifications

Product Overview

Environmental SpaceIndoor/Outdoor
Suitable ApplicationsFor outdoor and indoor use in structured (data) wiring systems such as industrial backbone, campus backbone, building backbone (riser) and/or horizontal cabling. For outdoor and indoor use in networks for industrial, telecom, cable TV and/or broadcast. Support all computer network applications such as FDDI, Gigabit Ethernet and ATM.

Construction

Fiber Cable Construction

Fiber TypeFiber CountSubunit Color
OM42Erika Violet
Fiber Color CodingTIA coding (Gxxxxxx.T): Blue

Buffer Specification

Fiber TypeBuffer ConstructionBuffer MaterialBuffer Diameter
OM4TightLSZH - Low Smoke Zero Halogen (Flame Retardant)0.9 mm
Central Strength MemberGRP
Cable Core Water TightYes
Cable Core WaterblockingWaterblock Tape
Bulk Cable Weight325 kg/km

SubUnit Specifications

Number of Active Subunits2
Number of Subunit Positions4
Fibers Per Subunit1

Jacket Specifications

Number of JacketsDouble Jacket
Type of ArmorSteel Wire

Inner Jacket

ColorErika Violet
Nom. Diameter2.1 mm
MaterialLSZH - Low Smoke Zero Halogen (Flame Retardant)

Outer Jacket Specifications

Outer Jacket

MaterialNominal DiameterRipcord
LSZH - Low Smoke Zero Halogen (Flame Retardant)11.6 mmYes
Table NotesStandard color: Black. Available colors: Orange, Yellow, Turquoise, Erika Violet, Red, Blue, Green, Brown, Violet, Pink, Grey, White, Black, Lime Green

Optical Characteristics

Max. Attenuation at 1300 nm0.9 dB/km
Max. Attenuation at 850 nm2.9 dB/km

Mechanical Characteristics

Mechanical Tests

DescriptionTested StandardRequirement/ValueAccording to Family Specification
Cable Min. Bend Radius Installation (Short Term)IEC 60794-1-21-E6232 mmIEC 60794-2-20
Cable Min. Bend Radius Operation (Long Term)IEC 60794-1-21-E11116 mmIEC 60794-2-20
Cable Max. Tensile Strength Installation (Short Term)IEC 60794-1-21-E13750 N (843 lbf)IEC 60794-2-20
Cable Max. Tensile Strength Operation (Long Term)IEC 60794-1-21-E11250 N (281 lbf)IEC 60794-2-20
Cable Max. Crush Resistance Installation (Short Term)IEC 60794-1-21-E322 kN/mIEC 60794-2-20
Cable Max. Crush Resistance Operation (Long Term)IEC 60794-1-21-E311 kN/mIEC 60794-2-20

Temperature Range

Operating Temperature Range-30 °C to +70 °C
Installation Temperature Range-5 °C to +50 °C
Storage Temperature Range-30 °C to +70 °C

Standards

UL Rating/Flame TestNon-UL Rated
IEC FlammabilityIEC 60332-1-2
IEC 60754-1 - Halogen AmountZero
IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity10 µS/mm
IEC 60754-2 - Halogen Acid Gas Amount - Min. pH4.3
REACHCompliant
ISO/IEC ComplianceIEC 60794
UV/ Sunlight ProtectionYes

History