Universal (Indoor/Outdoor) tight buffered fiber with Steel Wire Braid optical fiber distribution cable with Low Smoke Zero Halogen outer jacket. 24 fibers MM OM1.
Specifications
Specifications
Product Overview
Environmental Space | Indoor/Outdoor |
---|
Suitable Applications | For outdoor and indoor use in structured (data) wiring systems such as industrial backbone, campus backbone, building backbone (riser) and/or horizontal cabling. For outdoor and indoor use in networks for industrial, telecom, cable TV and/or broadcast. Support all computer network applications such as FDDI, Gigabit Ethernet and ATM. Not suitable for blown installation. |
---|
Construction
Fiber Cable Construction
Fiber Type | Fiber Count |
---|
OM1 | 24 |
Fiber Color Coding | TIA coding (Gxxxxxx.T): Blue, Orange, Green, Brown, Gray, White, Red, Black, Yellow, Violet, Pink, Aqua. With Ringmark: BL, OR, GR, BR, GY, WT, RD, BK, YL, VT, PK, AQ |
---|
Buffer Specification
Fiber Type | Buffer Construction | Buffer Material | Buffer Diameter |
---|
OM1 | Tight | LSZH - Low Smoke Zero Halogen (Flame Retardant) | 0.9 mm |
Cable Core Water Tight | Yes |
---|
Cable Core Waterblocking | Waterblocking Glass Yarns |
---|
Bulk Cable Weight | 194 kg/km |
---|
Jacket Specifications
Number of Jackets | Double Jacket |
---|
Type of Armor | Steel Wire Braid |
---|
Inner Jacket
Material | LSZH - Low Smoke Zero Halogen (Flame Retardant) |
---|
Outer Jacket Specifications
Outer Jacket
Material | Nominal Diameter | Ripcord |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | 13.7 mm | No |
Table Notes | Standard color: Orange. Available colors: Orange, Yellow, Turquoise, Erika Violet, Red, Blue, Green, Brown, Violet, Pink, Grey, White, Black, Lime Green |
---|
Optical Characteristics
Max. Attenuation at 1300 nm | 0.9 dB/km |
---|
Max. Attenuation at 850 nm | 3.4 dB/km |
---|
Mechanical Characteristics
Mechanical Tests
Description | Tested Standard | Requirement/Value | According to Family Specification |
---|
Cable Min. Bend Radius Installation (Short Term) | IEC 60794-1-21-E6 | 274 mm | IEC 60794-2-20 |
Cable Min. Bend Radius Operation (Long Term) | IEC 60794-1-21-E11 | 205.5 mm | IEC 60794-2-20 |
Cable Max. Tensile Strength Installation (Short Term) | IEC 60794-1-21-E1 | 1940 N (436 lbf) | IEC 60794-2-20 |
Cable Max. Crush Resistance Installation (Short Term) | IEC 60794-1-21-E3 | 22 kN/m | IEC 60794-2-20 |
Cable Max. Crush Resistance Operation (Long Term) | IEC 60794-1-21-E3 | 11 kN/m | IEC 60794-2-20 |
Temperature Range
Operating Temperature Range | -30 °C to +70 °C |
---|
Installation Temperature Range | -5 °C to +50 °C |
---|
Storage Temperature Range | -30 °C to +70 °C |
---|
Standards
UL Rating/Flame Test | Non-UL Rated |
---|
IEC Flammability | IEC 60332-1-2 |
---|
Reaction to Fire - Bundle Flame Test | IEC 60332-3-22 |
---|
IEC 60754-1 - Halogen Amount | Zero |
---|
IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity | 10 µS/mm |
---|
IEC 60754-2 - Halogen Acid Gas Amount - Min. pH | 4.3 |
---|
IEC 61034-2 - Smoke Density Min. Transmittance | 80% |
---|
REACH | Compliant |
---|
ISO/IEC Compliance | IEC 60794 |
---|
UV/ Sunlight Protection | Yes |
---|
History
Update and Revision | Revision Number: 0.80 Revision Date: 01-20-2023 |
---|
Documentation
Catalogs
Flyers
Videos
White Papers
Training
Data Sheets