Belden

GUSLE04 - Universal OFC CLT (LU S1085 A4): GLASS YARNS(1500N) + LSZH with 1 Tube of Ø3.3mm (OD 6.5mm) 4f MM OM4. CPR Dca.

(No reviews yet) Write a Review
SKU:
GUSLE04
Shipping:
Calculated at Checkout
$0.00

Description

Universal (Indoor/Outdoor) optical fiber (London Underground Certified; LU S1085 A4) Central Loose Tube cable with glass yarns (standard rodent protection) as strength member and Low Smoke Zero Halogen outer jacket. Product feature: This cable has standard rodent protection by glass yarns. Existing out of 1 Tube with a diameter of 3.3mm and cable diameter of 6.5mm with 4 fibers MM OM4. CPR Euroclass Dca.

Specifications

Specifications

Product Overview

Environmental SpaceIndoor/Outdoor - Euroclass Dca
Suitable ApplicationsFor outdoor and indoor use in structured (data) wiring systems such as industrial backbone, campus backbone, building backbone (riser) and/or horizontal cabling. For outdoor and indoor use in networks for industrial, telecom, cable TV and/or broadcast. Easy to install in ducts, tunnels and/or tubes. The cable has been designed to meet the requirements of LUL 1-085 standard.

Construction

Fiber Cable Construction

Fiber TypeFiber CountSubunit Color
OM44TIA coding (Gxxxxxx.T): Natural
Fiber Color CodingTIA coding (Gxxxxxx.T): Blue, Orange, Green, Brown
Cable Core Water TightYes
Cable Core WaterblockingWaterblocking Glass Yarns
Bulk Cable Weight48 kg/km

SubUnit Specifications

Number of Active Subunits1
Number of Subunit Positions1
Fibers Per Subunit4

Jacket Specifications

Number of JacketsSingle Jacket
Type of ArmorNon-Armored

Outer Jacket Specifications

Outer Jacket

MaterialNominal DiameterRipcord
LSZH - Low Smoke Zero Halogen (Flame Retardant)6.5 mmNo
Table NotesStandard color: Orange. Available colors: Orange, Yellow, Turquoise, Erika Violet, Red, Blue, Green, Brown, Violet, Pink, Grey, White, Black, Lime Green

Optical Characteristics

Max. Attenuation at 1300 nm0.9 dB/km
Max. Attenuation at 850 nm2.9 dB/km

Mechanical Characteristics

Mechanical Tests

DescriptionTested StandardRequirement/ValueAccording to Family Specification
Cable Min. Bend Radius Installation (Short Term)IEC 60794-1-21-E6130 mmIEC 60794-3-10
Cable Min. Bend Radius Operation (Long Term)IEC 60794-1-21-E1165 mmIEC 60794-3-10
Cable Max. Tensile Strength Installation (Short Term)IEC 60794-1-21-E11500 N (337 lbf)IEC 60794-3-10
Cable Max. Tensile Strength Operation (Long Term)IEC 60794-1-21-E1500 N (112 lbf)IEC 60794-3-10
Cable Max. Crush Resistance Installation (Short Term)IEC 60794-1-21-E315 kN/mIEC 60794-3-10
Cable Max. Crush Resistance Operation (Long Term)IEC 60794-1-21-E37.5 kN/mIEC 60794-3-10

Temperature Range

Operating Temperature Range-5 °C to +40 °C
Installation Temperature Range-5 °C to +40 °C
Storage Temperature Range-5 °C to +40 °C

Standards

UL Rating/Flame TestNon-UL Rated
IEC FlammabilityIEC 60332-1-2
Reaction to Fire - Bundle Flame TestIEC 60332-3-25
IEC 60754-1 - Halogen AmountZero
IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity10 µS/mm
IEC 60754-2 - Halogen Acid Gas Amount - Min. pH4.3
IEC 61034-2 - Smoke Density Min. Transmittance60%
CPR EuroclassDca-s2,d1,a1
REACHCompliant
ISO/IEC ComplianceIEC 60794
Safety ListingLUL 1-085
UV/ Sunlight ProtectionYes

History

Update and RevisionRevision Number: 0.51 Revision Date: 01-20-2023
View AllClose