Universal (Indoor/Outdoor) optical fiber Central Loose Tube (jelly filled tube) cable with glass yarns (standard rodent protection) as strength member and Low Smoke Zero Halogen outer jacket. Product feature: This cable has standard rodent protection by glass yarns. Existing out of 1 Tube with a diameter of 3.3mm with 16 fibers MM OM1. DNV approval.
Specifications
Specifications
Product Overview
| Environmental Space | Indoor/Outdoor |
|---|
| Suitable Applications | For outdoor and indoor use in structured (data) wiring systems such as industrial backbone, campus backbone, building backbone (riser) and/or horizontal cabling. For outdoor and indoor use in networks for industrial, telecom, cable TV and/or broadcast. Easy to install in ducts, tunnels and/or tubes. |
|---|
Construction
Fiber Cable Construction
| Fiber Type | Fiber Count | Subunit Color |
|---|
| OM1 | 16 | TIA coding (Gxxxxxx.T): Natural |
| Fiber Color Coding | TIA coding (Gxxxxxx.T): Blue, Orange, Green, Brown, Gray, White, Red, Black, Yellow, Violet, Pink, Aqua. With Ringmark: BL, OR, GR, BR |
|---|
| Cable Core Water Tight | Yes |
|---|
| Cable Core Waterblocking | Waterblocking Glass Yarns |
|---|
| Bulk Cable Weight | 70 kg/km |
|---|
SubUnit Specifications
| Number of Active Subunits | 1 |
|---|
| Number of Subunit Positions | 1 |
|---|
| Fibers Per Subunit | 16 |
|---|
Jacket Specifications
| Number of Jackets | Single Jacket |
|---|
| Type of Armor | Non-Armored |
|---|
Outer Jacket Specifications
Outer Jacket
| Material | Nominal Diameter | Ripcord |
|---|
| LSZH - Low Smoke Zero Halogen (Flame Retardant) | 7.6 mm | No |
| Table Notes | Standard color: Orange. Available colors: Orange, Yellow, Turquoise, Erika Violet, Red, Blue, Green, Brown, Violet, Pink, Grey, White, Black, Lime Green |
|---|
Optical Characteristics
| Fiber Core Diameter | 62.5 µm |
|---|
| Max. Attenuation at 1300 nm | 0.9 dB/km |
|---|
| Max. Attenuation at 850 nm | 3.4 dB/km |
|---|
Mechanical Characteristics
Mechanical Tests
| Description | Tested Standard | Requirement/Value | According to Family Specification |
|---|
| Cable Min. Bend Radius Installation (Short Term) | IEC 60794-1-21-E6 | 152 mm | IEC 60794-3-10 |
| Cable Min. Bend Radius Operation (Long Term) | IEC 60794-1-21-E11 | 76 mm | IEC 60794-3-10 |
| Cable Max. Tensile Strength Installation (Short Term) | IEC 60794-1-21-E1 | 760 N (171 lbf) | IEC 60794-3-10 |
| Cable Max. Tensile Strength Operation (Long Term) | IEC 60794-1-21-E1 | 500 N (112 lbf) | IEC 60794-3-10 |
| Cable Max. Crush Resistance Installation (Short Term) | IEC 60794-1-21-E3 | 15 kN/m | IEC 60794-3-10 |
| Cable Max. Crush Resistance Operation (Long Term) | IEC 60794-1-21-E3 | 7.5 kN/m | IEC 60794-3-10 |
Temperature Range
| Operating Temperature Range | -30 °C to +70 °C |
|---|
| Installation Temperature Range | -5 °C to +50 °C |
|---|
| Storage Temperature Range | -30 °C to +70 °C |
|---|
Standards
| UL Rating/Flame Test | Non-UL Rated |
|---|
| IEC Flammability | IEC 60332-1-2 |
|---|
| Reaction to Fire - Bundle Flame Test | IEC 60332-3-22 |
|---|
| IEC 60754-1 - Halogen Amount | Zero |
|---|
| IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity | 10 µS/mm |
|---|
| IEC 60754-2 - Halogen Acid Gas Amount - Min. pH | 4.3 |
|---|
| IEC 61034-2 - Smoke Density Min. Transmittance | 80% |
|---|
| REACH | Compliant |
|---|
| ISO/IEC Compliance | IEC 60794 |
|---|
| UV/ Sunlight Protection | Yes |
|---|
History
| Update and Revision | Revision Number: 0.25 Revision Date: 01-20-2023 |
|---|
Documentation
Brochures and Guides
All Resources
Data Sheets