Universal (Indoor/Outdoor) tight buffered optical fiber cable with glass yarns as strength member and improved rodent protection with Low Smoke Zero Halogen outer jacket. 12 fibers SM OS2 G.657.A2. CPR Euroclass Dca.
Specifications
Specifications
Product Overview
Environmental Space | Indoor/Outdoor - Euroclass Dca |
---|
Suitable Applications | For outdoor and indoor use in structured (data) wiring systems such as industrial backbone, campus backbone, building backbone (riser) and/or horizontal cabling. For outdoor and indoor use in networks for industrial, telecom, cable TV and/or broadcast. Support all computer network applications such as FDDI, Gigabit Ethernet and ATM. Not suitable for blown installation. |
---|
Construction
Fiber Cable Construction
Fiber Type | Fiber Grade acc. ITU-T | Fiber Count |
---|
OS2 | G.657A2 | 12 |
Fiber Color Coding | TIA coding (Gxxxxxx.T): Blue, Orange, Green, Brown, Gray, White, Red, Black, Yellow, Violet, Pink, Aqua |
---|
Buffer Specification
Fiber Type | Buffer Construction | Buffer Material | Buffer Diameter |
---|
OS2 | Tight | LSZH - Low Smoke Zero Halogen (Flame Retardant) | 0.9 mm |
Cable Core Water Tight | Yes |
---|
Cable Core Waterblocking | Waterblocking Glass Yarns |
---|
Bulk Cable Weight | 76 kg/km |
---|
Jacket Specifications
Number of Jackets | Single Jacket |
---|
Type of Armor | Non-Armored |
---|
Outer Jacket Specifications
Outer Jacket
Material | Nominal Diameter | Ripcord |
---|
LSZH - Low Smoke Zero Halogen (Flame Retardant) | 9.4 mm | No |
Table Notes | Standard color: Orange. Available colors: Orange, Yellow, Turquoise, Erika Violet, Red, Blue, Green, Brown, Violet, Pink, Grey, White, Black, Lime Green |
---|
Optical Characteristics
Max. Attenuation at 1310 nm | 0.40 dB/km |
---|
Max. Attenuation at 1550 nm | 0.30 dB/km |
---|
Max. Attenuation at 1625 nm | 0.30 dB/km |
---|
Mechanical Characteristics
Mechanical Tests
Description | Tested Standard | Requirement/Value | According to Family Specification |
---|
Cable Min. Bend Radius Installation (Short Term) | IEC 60794-1-21-E6 | 188 mm | IEC 60794-2-20 |
Cable Min. Bend Radius Operation (Long Term) | IEC 60794-1-21-E11 | 94 mm | IEC 60794-2-20 |
Cable Max. Tensile Strength Installation (Short Term) | IEC 60794-1-21-E1 | 760 N (171 lbf) | IEC 60794-2-20 |
Cable Max. Crush Resistance Installation (Short Term) | IEC 60794-1-21-E3 | 5 kN/m | IEC 60794-2-20 |
Cable Max. Crush Resistance Operation (Long Term) | IEC 60794-1-21-E3 | 3 kN/m | IEC 60794-2-20 |
Temperature Range
Operating Temperature Range | -30 °C to +70 °C |
---|
Installation Temperature Range | -5 °C to +50 °C |
---|
Storage Temperature Range | -30 °C to +70 °C |
---|
Standards
UL Rating/Flame Test | Non-UL Rated |
---|
IEC Flammability | IEC 60332-1-2 |
---|
Reaction to Fire - Bundle Flame Test | IEC 60332-3-24 |
---|
IEC 60754-1 - Halogen Amount | Zero |
---|
IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity | 10 µS/mm |
---|
IEC 60754-2 - Halogen Acid Gas Amount - Min. pH | 4.3 |
---|
IEC 61034-2 - Smoke Density Min. Transmittance | 60% |
---|
CPR Euroclass | Dca-s1,d1,a1 |
---|
REACH | Compliant |
---|
ISO/IEC Compliance | IEC 60794 |
---|
UV/ Sunlight Protection | Yes |
---|
History
Update and Revision | Revision Number: 0.76 Revision Date: 01-20-2023 |
---|
Documentation
Catalogs
Flyers
Videos
White Papers
Training
Data Sheets