Transit Grade, Indoor/Outdoor, Multi-Loose-Tube, OS2, 12 Fibers, Dry Tubes 2.5mm, Corrugated Steel Tape, Double Jacket, Black, LSZH, OFCG-ST1
Specifications
Specifications
Product Overview
| Product Category | Fiber Multi-Loose Tube Cable |
|---|
| Suitable Applications | Extended Distance Horizontal & Backbone Data/Telco Network, Noisy Environment, Indoor/ Outdoor & Wet Locations, Armored, UV Resistant |
|---|
Fiber Specifications
| Fiber Type | OS2 |
|---|
| Fiber Core Diameter | 8.2/125 µm |
|---|
| Fiber Diameter | 250 µm |
|---|
| Fiber Color Coding | TIA-598-D |
|---|
Cable Construction
| Number of Active Subunits | 1 |
|---|
| Number of Fillers | 4 |
|---|
| Fibers Per Subunit | 12 |
|---|
| Subunit Waterblocking | Gel Free |
|---|
| Subunit Diameter | 0.098 in (2.5 mm) |
|---|
| Subunit Color | TIA-598-D |
|---|
| Central Strength Member | GRP |
|---|
Inner Jacket Specifications
| Strength Member | Fiberglass Yarns |
|---|
| Material | LSZH - Low Smoke Zero Halogen (Flame Retardant) |
|---|
| Nom. Diameter | 0.455 in (11.6 mm) |
|---|
| Color | Black |
|---|
| Number of Ripcords | 1 |
|---|
Armor Specifications
| Armor Type and Material | CST - Corrugated Steel Tape |
|---|
Outer Jacket Specifications
| Strength Member | Fiberglass Yarns |
|---|
| Jacket Material | LSZH - Low Smoke Zero Halogen (Flame Retardant) |
|---|
| Nom. Diameter | 0.690 in (17.5 mm) |
|---|
| Number of Ripcords | 2 |
|---|
Optical Characteristics
| Wavelength | 1310 nm | 1550 nm |
|---|
| Max. Attenuation | 0.35 | 0.25 |
| Mode Field Diameter | 9.2 µm | 10.4 µm |
| 1 Gigabit Ethernet Performance | 5000 m | |
| 10 Gigabit Ethernet Performance | 10000 m | 40000 m |
Mechanical Characteristics
| Min. Bend Radius During Installation | 20x Cable OD |
|---|
| Min. Bend Radius During Operation | 10x Cable OD |
|---|
| Max. Tensile Strength During Installation | 2670 N (600 lbf) |
|---|
| Max. Tensile Strength During Operation | 800 N (180 lbf) |
|---|
| Crush Resistance | 220 N/cm |
|---|
| Bulk Cable Weight | 214 lbs/kft (318 kg/km) |
|---|
Temperature Range
| Installation Temperature Range | -10°C to +60°C |
|---|
| Operating Temperature Range | -40°C to +70°C |
|---|
| Storage Temperature Range | -40°C to +70°C |
|---|
Standards and Compliance
| Environmental Suitability | Indoor/Outdoor, Sunlight Resistance, Burial |
|---|
| Flammability / Reaction to Fire | UL 1685 FT4 Loading, Limited Smoke, FT4 |
|---|
| NEC / UL Compliance | OFCG-ST1 |
|---|
| ICEA Compliance | S-104-696 |
|---|