Belden

TU-3LG-144-RT2 - Tray, In+Outdoor, MLT, OM3, 144f, Gel Tubes 2.8mm, CST, Dbl Jkt, Blk, CPE, OFCR, Oil Res 1/2

(No reviews yet) Write a Review
SKU:
TU-3LG-144-RT2
Shipping:
Calculated at Checkout
$0.00

Description

DataTuff Tray, Indoor/Outdoor, Multi-Loose-Tube, OM3, 144 Fibers, Gel Filled Tubes 2.8mm, Corrugated Steel Tape, Double Jacket, Black, CPE, OFCR, Oil Res 1 & 2

Specifications

Specifications

Product Overview

Product CategoryFiber Multi-Loose Tube Cable
Suitable ApplicationsExtended Distance Horizontal & Backbone Data/Telco Network, Noisy Environment, Indoor/Outdoor & Wet Locations, Rodent Proof

Fiber Specifications

Fiber TypeOM3
Fiber Core Diameter50/125 µm
Fiber Diameter250 µm
Fiber Count144
Fiber Color CodingTIA-598-D

Cable Construction

Number of Active Subunits12
Fibers Per Subunit12
Subunit WaterblockingGel Filled
Subunit Diameter0.110 in (2.8 mm)
Central Strength MemberUpjacketed GRP
Core WrapWaterblocking tape

Inner Jacket Specifications

Strength MemberWaterblocking Aramid Yarns
MaterialPVC - Polyvinyl Chloride
ColorBlack

Armor Specifications

Armor Type and MaterialCST - Corrugated Steel Tape

Outer Jacket Specifications

Jacket MaterialCPE - Chlorinated Polyethylene
Nom. Diameter0.880 in (22.4 mm)
Number of Ripcords2

Optical Characteristics

Wavelength850 nm1300 nm
Max. Attenuation3.01.0
1 Gigabit Ethernet Performance1000550
10 Gigabit Ethernet Performance300 m-
Min. Effective Modal Bandwidth (EMB)2000 MHz.km-
Min. Overfilled Launch (OFL) Bandwidth1500 MHz.km500 MHz.km

Mechanical Characteristics

Min. Bend Radius During Installation20x Cable OD
Min. Bend Radius During Operation10x Cable OD
Max. Tensile Strength During Installation2670 N (600 lbf)
Max. Tensile Strength During Operation800 N (180 lbf)
Crush Resistance220 N/cm
Bulk Cable Weight295 lbs/kft (439 kg/km)

Temperature Range

Installation Temperature Range-10°C to +60°C
Operating Temperature Range-40°C to +70°C
Storage Temperature Range-40°C to +70°C

Standards and Compliance

Environmental SuitabilityIndoor/Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireOFCR, FT4
ICEA ComplianceS-104-696

History

Update and RevisionRevision Number: 0.7 Revision Date: 07-07-2022