LioN-M, I/O Standalone, DeviceNet, industrial plastic housing, 60 mm, IP67, 16 digital in-/output channels (universal I/O) (1.6 A), 8 x M12 A-coded I/O connection, 5-poles, 2 x 7/8" bus and system supply connection, 5-poles, 2 x 7/8" actuator power supply connection, 4-poles
Specifications
Specifications
| Product Family | I/O Systems: Active - Standalone |
|---|
| Product Sub Family | LioN-M |
|---|
| Item Description | 0930 DSL 700 |
|---|
| Device Type | I/O Module |
|---|
| Protocol | DeviceNet |
|---|
| I/O Function | 16DIO |
|---|
| Bus Connection | 7/8", 5-poles |
|---|
| Power Connection (System Supply) | 7/8" Power, 4-poles |
|---|
| I/O Connection | M12, 5-poles, A-coded |
|---|
| I/O Type | Digital In-/Output (Universal) |
|---|
Product Life Cycle
| Housing Material | PBT + ASA |
|---|
General Data
| Protection Degree / IP Rating** | IP67 |
|---|
| Housing Color | Black |
|---|
| Potted | No |
|---|
| Dimensions (W x H x D) | 60 mm x 40 mm x 243 mm |
|---|
| Weight | 390 g |
|---|
| Ambient Temperature (Operation)* | -10 °C to 60 °C |
|---|
| Vibration Resistance | 10 g / 5 -500 Hz |
|---|
| Shock Resistance | 50 g / 11ms |
|---|
| Contact Base Material | M12, A-coded, CuSn, Gold-plated | 7/8" CuZn, Gold-plated |
|---|
| Contact Bearer Material | PA / TPU |
|---|
| O-Ring Material | FKM |
|---|
| Mounting | 2 hole screw mounting. Use standard M4 x 25 / 30 screws with toothed lock washer (as per DIN 125) and self-locking nuts. |
|---|
| Fastening Torque (Fixing Screw) | M4: 1 Nm |
|---|
| Fastening Torque (Ground Connection (FE)) | M4: 1 Nm |
|---|
| Fastening Torque (Bus Connection) | M12: 0.5 Nm |
|---|
| Fastening Torque (Power Connection) | 7/8": 1.5 Nm |
|---|
| Fastening Torque (I/O Connection) | M12: 0.5 Nm |
|---|
| Included in Delivery | Attachable Labels: 15x, Sealing Caps: 4x M12 |
|---|
DeviceNet
| Connection | 7/8", 5-poles |
|---|
| Number of Connections | 2 |
|---|
| Transmission Rate | 125 kbps ... 500 kbps |
|---|
| Transmission Rate Adjustment | Automatic |
|---|
| Addressing via Rotary Address Switches | 0…63 dec |
|---|
| Addressing via DeviceNet | 99 dec |
|---|
| Product Code | 36 |
|---|
Power Supply
| Connection Module Supply Voltage | 7/8" Power, 4-poles |
|---|
| Number of Connections | 2 |
|---|
| Current Carrying Capacity of Connector | max. 9 A |
|---|
| Module Supply Voltage (Nominal) | 24 V DC (SELV/PELV) |
|---|
| Module Supply Voltage (Range) | 19 V DC to 30 V DC |
|---|
| Current Consumption (typ.) | 70 mA (at 24 V DC) |
|---|
| Reverse Polarity Protection | Yes |
|---|
| Status Indicator (System Supply) | LED green |
|---|
| Diagnostic Indicator | No |
|---|
| Connection Sensor Supply Voltage | 7/8" Power, 4-poles |
|---|
| Number of Connections | 2 |
|---|
| Current Carrying Capacity of Connector | max. 9 A |
|---|
| Sensor Supply Voltage (Nominal) | 24 V DC (SELV/PELV) |
|---|
| Sensor Supply Voltage (Range) | 19 V DC to 30 V DC |
|---|
| Reverse Polarity Protection | Yes |
|---|
| Status Indicator (Sensor Supply) | LED green |
|---|
| Diagnostic Indicator | No |
|---|
| Connection Actuator Supply Voltage | 7/8" Power, 4-poles |
|---|
| Number of Connections | 2 |
|---|
| Current Carrying Capacity of Connector | max. 9 A |
|---|
| Actuator Supply Voltage (Nominal) | 24 V DC (SELV/PELV) |
|---|
| Actuator Supply Voltage (Range) | 19 V DC to 30 V DC |
|---|
| Reverse Polarity Protection | Yes |
|---|
| Status Indicator (Actuator Supply) | LED green |
|---|
| Diagnostic Indicator | No |
|---|
Digital Input Channels
| Number of Digital Input Channels | max. 16, universal |
|---|
| Connection | M12, 5-poles, A-coded |
|---|
| Number of Ports | 8x, X1 to X8 |
|---|
| Channel Type | Type 3 acc. to IEC 61131-2 |
|---|
| Sensor Current Supply | max. 200 mA per port (at 30°C) |
|---|
| Input Wiring | 2-, 3-, 4-wire |
|---|
| Nominal Voltage | 24 V DC via US (module power supply) |
|---|
| Nominal Current | typ. 5 mA |
|---|
| Sensor Type | PNP |
|---|
| Input Voltage Range "0" signal | -3 V DC …+5 V DC |
|---|
| Input Voltage Range "1" signal | 11 V DC … 30 V DC |
|---|
| Input Filter Time | 1 ms, fixed |
|---|
| Protective Circuit | Electronicaly: Overload protection, short-circuit protection |
|---|
| Status Indicator (Inputs) | LED yellow per channel |
|---|
| Diagnostic Indicator | LED red per port |
|---|
Digital Output Channels
| Number of Digital Output Channels | max. 16, universal |
|---|
| Connection | M12, 5-poles, A-coded |
|---|
| Number of Ports | 8x, X1 to X8 |
|---|
| Channel Type | p-switching |
|---|
| Output Current per Channel | max. 1.6 A |
|---|
| Output Wiring | 2-, 3-wire |
|---|
| Nominal Voltage | 24 V DC via UL (actuator power supply) |
|---|
| Output Current per Module | max. 9 A |
|---|
| Galvanically Isolated | No |
|---|
| Protective Circuit | Electronicaly: Overload protection, short-circuit protection |
|---|
| Overload Behavior | Auto off and on switching / Manual restart |
|---|
| Status Indicator (Outputs) | LED yellow per channel |
|---|
| Diagnostic Idicator | LED red per channel |
|---|
Electrical Isolation
| US (System Supply Voltage) / FE | 500 V DC |
|---|
| US / UL (Actuator Supply Voltage) | 500 V DC |
|---|
| UL / FE | 500 V DC |
|---|
| Bus connection / FE | 500 V DC |
|---|
EMC Conformance
| EMC Directive | 2014/30/EU |
|---|
| EN 61000-4-2 Electrostatic Discharge (ESD) | Criterion B; 4 kV contact discharge, 8 kV air discharge |
|---|
| EN 61000-4-3 Electromagnetic Field | Criterion A; Field intensity: 10 V/m |
|---|
| EN 61000-4-4 Fast Transients (Burst) | Criterion B, 2 kV |
|---|
| EN 61000-4-5 Surge Voltage | Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical); For I/O ports with cables ≤ 30m |
|---|
| EN 61000-4-6 Conducted immunity | Criterion A; Test voltage 10 V |
|---|
| EN 55022 Radio Interference Properties | Class A |
|---|
Safety & Environmental Compliance
Approvals
| UL | cULus Listed, UL 508 |
|---|
| UL-File | E230848 |
|---|
Notes
| Protection Degree / IP Rating Note | ** only if mounted and locked in combination with Hirschmann / Lumberg Automation connector. |
|---|
| System Power Supply Connection Note | *do not connect / disconnect under voltage! |
|---|
| Update and Revision | Revision Number: 0.69 Revision Date: 05-24-2023 |
|---|