Twelve 16 AWG stranded (7x24) bare copper conductors plus bare copper ground wire, cross-linked polyethylene insulation, PVC inner jacket, aluminum interlocked armor, PVC outer jacket.
Specifications
Specifications
Product Overview
| Suitable Applications | Power and Control Applications up to 600V |
|---|
Construction Details
Conductor
| Element | Number of Element | Size | Stranding | Material |
|---|
| Conductor(s) | 12 | 16 AWG | 7x24 | BC - Bare Copper |
| Ground Wire | 1 | 16 AWG | 7x24 | BC - Bare Copper |
Insulation
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|
| Conductor(s) | XLP, XLPO, XLPE (Thermoset) | 0.030 in (0.76 mm) | 0.118 in (3.00 mm) | White and Numbered, Black and Numbered |
| Ground Wire | XLP, XLPO, XLPE (Thermoset) | 0.030 in (0.76 mm) | 0.118 in (3.00 mm) | Green |
Outer Shield
Inner Jacket
| Material | Nom. Thickness | Nom. Diameter | Ripcord | Color |
|---|
| PVC - Polyvinyl Chloride | 0.63 in (16 mm) | 0.651 in (16.5 mm) | Yes | Black |
| Table Notes | Separator-CORR. MYLAR Tape |
|---|
Armor
| Armor Type & Material | Armor Thickness | Diameter Over Armor |
|---|
| AIA - Aluminum Interlock Armor | 0.025 in (0.64 mm) | 0.876 in (22.3 mm) |
Outer Jacket
| Material | Nom. Thickness | Nom. Diameter |
|---|
| PVC - Polyvinyl Chloride | 0.052 in (1.3 mm) | 0.980 in |
| Overall Cable Diameter (Nominal) | 0.980 in |
|---|
Electrical Characteristics
Electricals
| Element | Nom. Conductor DCR | Max. Current |
|---|
| Conductor(s) | 4.45 Ohm/1000ft | 12.6 Amps per Conductor at 30ºC |
| Ground Wire | 4.45 Ohm/1000ft (14.6 Ohm/km) | 19 Amps per Conductor at 25ºC |
Voltage
Mechanical Characteristics
Temperature
Bend Radius
| Stationary Min. | Installation Min. |
|---|
| 11.76 in (298.7 mm) | 11.76 in |
| Max. Pull Tension | 464.1 lbs (210.5 kg) |
|---|
| Bulk Cable Weight | 425 lbs/1000ft |
|---|
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial |
|---|
| CEC / C(UL) Compliance | HL, ACIC |
|---|
| European Directive Compliance | EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
|---|
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
|---|
History
| Update and Revision | Revision Number: 0.196 Revision Date: 12-20-2022 |
|---|
Documentation
Product Bulletins
Catalogs
Standards
Compliance Documentation
Data Sheets