Description

Canadian Instrumentation Cable TC-ACIC 600V, 40+G Conductor 16AWG (7x24) Bare Copper, XLPE Insulation, PVC Inner Jacket, Aluminum Interlock Armor, Blue PVC Outer Jacket, 90C Dry/Wet CSA HL SUN RES -40C

Specifications

Specifications

Put-Up TypeReel

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V

Construction Details

Conductor

ElementNumber of ElementSizeStrandingMaterial
Conductor(s)4016 AWG7x24BC - Bare Copper
Ground Wire116 AWG7x24BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)XLP, XLPO, XLPE (Thermoset)0.030 in (0.76 mm)0.118 in (3.00 mm)White and Numbered, Black and Numbered
Ground WireXLP, XLPO, XLPE (Thermoset)0.030 in (0.76 mm)0.118 in (3.00 mm)Green

Outer Shield

Material
No Shield

Inner Jacket

MaterialNom. ThicknessNom. DiameterRipcordColor
PVC - Polyvinyl Chloride0.083 in (2.1 mm)1.069 in (27.15 mm)YesBlack

Armor

Armor Type & MaterialArmor ThicknessDiameter Over Armor
AIA - Aluminum Interlock Armor0.034 in (0.86 mm)1.329 in (33.76 mm)
Table NotesSeprator -Corrugated Mylar Tape

Outer Jacket

MaterialNom. ThicknessNom. Diameter
PVC - Polyvinyl Chloride0.052 in (1.3 mm)1.433 in
1.41 in
Overall Cable Diameter (Nominal)1.410 in

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)4.2 Ohm/1000ft10.8 Amps per Conductor at 30ºC
Ground Wire4.2 Ohm/1000ft (14 Ohm/km)10 Amps per Conductor at 25ºC

Voltage

Voltage Rating
600 V

Mechanical Characteristics

Temperature

Operating
-40°C To +90°C

Bend Radius

Stationary Min.Installation Min.
16.91 in (429.5 mm)16.91 in
Max. Pull Tension1664 lbs (754.8 kg)
Bulk Cable Weight1016 lbs/1000ft

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
CEC / C(UL) ComplianceHL, ACIC
European Directive ComplianceEU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.211 Revision Date: 12-20-2022
View AllClose