Belden

29023 - ACIC 600V, 15+G C #16 Str BC, XLPE Ins, PVC Jkt, AIA Armor, Blu PVC Jkt, 90C Dry/Wet CSA HL SUN RES -40C

(No reviews yet) Write a Review
SKU:
29023
Shipping:
Calculated at Checkout
$0.00

Description

Canadian Instrumentation Cable TC-ACIC 600V, 15+G Conductor 16AWG (7x24) Bare Copper, XLPE Insulation, PVC Inner Jacket, Aluminum Interlock Armor, Blue PVC Outer Jacket, 90C Dry/Wet CSA HL SUN RES -40C

Specifications

Specifications

Put-Up TypeReel

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V

Construction Details

Conductor

ElementNumber of ElementSizeStrandingMaterial
Conductor(s)1516 AWG7x24BC - Bare Copper
Ground Wire116 AWG7x24BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)XLP, XLPO, XLPE (Thermoset)0.030 in (0.76 mm)0.118 in (3.00 mm)White and Numbered, Black and Numbered, [Delete]
Ground WireXLP, XLPO, XLPE (Thermoset)0.030 in (0.76 mm)0.118 in (3.00 mm)Green

Outer Shield

Material
No Shield

Inner Jacket

MaterialNom. ThicknessNom. DiameterRipcordColor
PVC - Polyvinyl Chloride0.063 in (1.6 mm)0.685 in (17.4 mm)YesBlack

Armor

Armor Type & MaterialArmor ThicknessDiameter Over Armor
AIA - Aluminum Interlock Armor0.025 in (0.64 mm)0.910 in (23.1 mm)
Table NotesSeprator -Corrugated Mylar Tape

Outer Jacket

MaterialNom. ThicknessNom. Diameter
PVC - Polyvinyl Chloride0.052 in (1.3 mm)1.014 in
Overall Cable Diameter (Nominal)1.014 in

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)4.2 Ohm/1000ft12.6 Amps per Conductor at 30ºC
Ground Wire4.2 Ohm/1000ft (14 Ohm/km)10 Amps per Conductor at 25ºC

Voltage

Voltage Rating
600 V

Mechanical Characteristics

Temperature

Operating
-40°C To +90°C

Bend Radius

Stationary Min.Installation Min.
12.12 in (307.8 mm)12.12 in
Max. Pull Tension771 lbs (350 kg)
Bulk Cable Weight474 lbs/1000ft

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
CEC / C(UL) ComplianceHL, ACIC
European Directive ComplianceEU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.204 Revision Date: 12-20-2022
View AllClose