Canadian Instrumentation Cable TC-ACIC 600V, 8+G Conductor 18AWG (7x26) Bare Copper, XLPE Insulation, PVC Inner Jacket, Aluminum Interlock Armor, Blue PVC Outer Jacket, 90C Dry/Wet CSA HL SUN RES -40C
Specifications
Specifications
Product Overview
| Suitable Applications | Power and Control Applications up to 600V | 
|---|
Construction Details
Conductor
| Element | Number of Element | Size | Stranding | Material | 
|---|
| Conductor(s) | 8 | 18 AWG | 7x26 | BC - Bare Copper | 
| Ground Wire | 1 | 16 AWG | 7x26 | BC - Bare Copper | 
Insulation
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code | 
|---|
| Conductor(s) | XLP, XLPO, XLPE (Thermoset) | 0.030 in (0.76 mm) | 0.106 in (2.69 mm) | White and Numbered, Black and Numbered, [Delete] | 
| Ground Wire | XLP, XLPO, XLPE (Thermoset) | 0.030 in (0.76 mm) | 0.106 in (2.69 mm) | Green | 
Outer Shield
Inner Jacket
| Material | Nom. Thickness | Nom. Diameter | 
|---|
| PVC - Polyvinyl Chloride | 0.047 in (1.2 mm) | 0.482 in (12.2 mm) | 
Armor
| Armor Type & Material | Armor Thickness | Diameter Over Armor | 
|---|
| AIA - Aluminum Interlock Armor | 0.025 in (0.64 mm) | 0.707 in (18.0 mm) | 
| Table Notes | Seprator -Corrugated Mylar Tape | 
|---|
Outer Jacket
| Material | Nom. Thickness | Nom. Diameter | Ripcord | 
|---|
| PVC - Polyvinyl Chloride | 0.052 in (1.3 mm) | 0.811 in | Yes | 
| Overall Cable Diameter (Nominal) | 0.811 in | 
|---|
Electrical Characteristics
Electricals
| Element | Nom. Conductor DCR | Max. Current | 
|---|
| Conductor(s) | 6.8 Ohm/1000ft | 9.8 Amps per Conductor at 30ºC | 
| Ground Wire | 6.8 Ohm/1000ft (22 Ohm/km) | 8 Amps per Conductor at 25ºC | 
Voltage
Mechanical Characteristics
Temperature
Bend Radius
| Stationary Min. | Installation Min. | 
|---|
| 9.73 in (247 mm) | 9.73 in | 
| Max. Pull Tension | 415 lbs (188 kg) | 
|---|
| Bulk Cable Weight | 269 lbs/1000ft | 
|---|
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial | 
|---|
| CEC / C(UL) Compliance | HL, ACIC | 
|---|
| European Directive Compliance | EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) | 
|---|
| APAC Compliance | China RoHS II (GB/T 26572-2011) | 
|---|
History
| Update and Revision | Revision Number: 0.208    Revision Date: 12-20-2022 | 
|---|
Documentation
Catalogs
Tools
Compliance Documentation
Data Sheets